101
Type of Event
Status to generate a ‘1’ in the log
Status to generate a ‘0’ in the log
Relay output
Relay activated
Relay not activated
Interlock DI
In the Interlock state as defined in
the Interlock page
In the non-Interlock state as defined in
the Interlock page
Level Switch DI In the Low Alarm state as defined
in the Level Switches page
In the Normal state as defined in the
Level Switches page
Generic DI –
Alarm selected
In the Alarm state as defined in the
Generic Inputs page
In the Normal state as defined in the
Generic Inputs page
Generic DI – No
Alarm selected
Switch closed
Switch open
A window will open to ask if you would like to open the file or save it to disk. Select the method
you would like to use. The file is .csv (comma separated variable) file that will open in a
spreadsheet such as Excel.
6.26 Relay (1 – 8) Output Menus – Feed After Another Relay (%) Types
This page is used to program to activate one relay for a percentage of the time that another relay
had been activated. The first relay will activate, and its on-time recorded. When the first relay
shuts off, the total on-time is calculated, and this relay is activated for the correct percentage of
that time. If you make changes to the Input Assignment, you will need to click on the “Submit”
button in order to see all the correct units.
You may also change the Relay Control Mode here. If you do, you will have to reselect the Input
Assignment as well.
This section assumes that the Relay Control Mode is set to Feed After Another Relay. Other
control mode types are described in other sections of the manual.
Relay Control Mode
Click on the arrow of the pull down menu and select the way that you want to control the relay.
See Section 6.2 for details on each control mode.
Assign Relay to Feed After
Click on the arrow of the pull down menu and select the relay that will be used to control this
relay.
Status
This displays the current status of the relay output, either “Off” or “On”, and if on, the amount of
time it has been on. Possible status messages are Off, Off/Manual, On/Time counting down and
On/Time counting down/Hand (for manual activation). The only possible error message is
Interlock. See section 8.1 for a complete description of error messages.
Custom Name
This menu allows you to call the output another name if desired. Type the new name in the text
box.
% of Relay to Feed
Use this menu to type in percentage of the assigned relay’s on-time desired for this relay.