Ethernet Card Failure
This error message is caused by a failure of the controller to recognize that the option circuit board
is connected.
Possible
Causes
Corrective
Actions
Poor connection of the option board to
Remove the option board and inspect both
the core board.
mating connectors for corrosion or damage.
Reinstall the option board.
Faulty Ethernet board.
Replace the board.
Temperature High Alarm
This error message is caused by the temperature signal from the conductivity sensor exceeding the
user-programmed value for the high alarm limit.
Possible
Causes
Corrective
Actions
The actual temperature is too high.
Correct problem with process.
The programmed value is set too close to
Go to the sensor input page and increase the
the normal operating temperature.
high alarm limit.
The temperature sensor has lost calibration.
Go to the Temperature Input Page and calibrate
the temperature.
Faulty circuit board.
Go to the Temperature Input Page and perform
a self test. If the self test fails, then the sensor
input board (if makeup) or the core interface
board (if system) should be replaced.
Faulty temperature sensor.
If a successful calibration is not possible,
the temperature sensor is probably faulty, and
the sensor should be replaced.