WAGO-I/O-SYSTEM 750
Fieldbus Communication 267
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Common Services
Table 194: Message router (02
hex
) – Common service
Service available
Service code
Class
Instance
Service-Name
Description
01
hex
Yes
No
Get_Attribute_All
Supplies contents of all attributes
0E
hex
No
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
Pos: 111.4 /Alle Serien (Allgemeine Module)/Feldbuskommunikation/EtherNetIP/Assembly (04hex), statische Assembly Instanz (Controller) @ 7\mod_1265639174189_21.doc @ 49994 @ 4 @ 1
12.3.5.6 Assembly Object (04
hex
)
Using the "Assembly" classe, even several diverse objects can be combined.
These could be, for example, input and output data, status and control information
or diagnostic information. WAGO uses the manufacturer-specific instances in
order to provide these objects for you in various arrangements. This gives you an
efficient way to exchange process data. The following is a description of the
individual static Assembly instances with their contents and arrangements.
Instance (Class Attributes)
Table 195: Assembly (04
hex
) – Class
Attribute ID Access
Name
Data type
Description
Default value
1
Get
Revision UINT
Revision of this object
2 (0x0002)
2 Get
Max
Instance
UINT Highest
Instance
111
(0x006F)
Overview of static Assembly instances
Table 196: Overview of static Assembly instances
Instance
Description
Instance 101 (65
hex
)
For analog and digital output data, as well as fieldbus input variables
Instance102 (66
hex
)
For digital output data and fieldbus input variables
Instance 103 (67
hex
)
For analog output data and fieldbus input variables
Instance 104 (68
hex
)
For analog and digital intput data, status and fieldbus output variables
Instance 105 (69
hex
)
For digital input data, status and fieldbus output variables
Instance 106 (6A
hex
) For analog input data, status and fieldbus output variables
Instance 107 (6B
hex
) For digital and analog input data and fieldbus output variables
Instance 108 (6C
hex
) For digital input data and fieldbus output variables
Instance109 (6D
hex
)
For analog input data and fieldbus output variables
Instance 110 (6E
hex
) For fieldbus output variables
Instance 111 (6F
hex
)
For fieldbus intput variables
Instance 101 (65
hex
)
This assembly instance contains analog and digital output data. Any fieldbus input
variables that may be defined are attached behind this.