WAGO-I/O-SYSTEM 750
I/O Modules 333
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Description
0 D0
C
DALI command,
DSI dimming value
Control byte
1 D2
D1 Parameter
2
DALI
Address
2
D4
D3
Command extension
Parameter 1
13.2.5.12 EnOcean Radio Receiver
750-642
The EnOcean radio receiver has a total of 4 bytes of user data in both the Input
and Output Process Image (3 bytes of module data and 1 byte of control/status).
The following tables illustrate the Input and Output Process Image, which have 2
words mapped into each image. Word alignment is applied.
Table 357: EnOcean Radio Receiver 750-642
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Description
0 D0
S Data
byte
Status
byte
1 D2
D1
Data
bytes
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Description
0
-
C
not used
Control byte
1 -
-
not
used
13.2.5.13 MP Bus Master Module
750-643
The MP Bus Master Module has a total of 8 bytes of user data in both the Input
and Output Process Image (6 bytes of module data and 2 bytes of control/status).
The following table illustrates the Input and Output Process Image, which have 4
words mapped into each image. Word alignment is applied.
Table 358: MP Bus Master Module 750-643
Input and Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Description
0 C1/S1
C0/S0
extended
Control/
Status byte
Control/status
byte
1 D1
D0
2 D3
D2
3 D5
D4
Data bytes