198 Diagnostics
WAGO-I/O-SYSTEM
750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
Table 70: Blink code table for the I/O LED signaling, error code 14
Error code 14: "Error in external storage (memory card)"
Error
Argument
Error Description
Solution
1
Memory card cannot be
used (message from
driver)
1. Replace the memory card with a new one.
2. Should this error persist, contact I/O Support..
2
Function cancelled by
the user (30 s)
1. Plug in the memory card.
2. a) During the system start:
Restart the fieldbus controller by switching the power
supply off and on.
b) In ongoing operation:
Restart the access function.
3
Internal memory is full
1. Check the internal file system and the /copy/
directory on the memory card.
The size of the /copy/ directory may not exceed the
total size of the internal file system!
2. If necessary, delete files (e.g. through FTP,
formatting the internal drive or cleaning the memory
card on the PC).
4
Memory card is full
1. Use the PC to create storage space on the memory
card or replace the memory card with a new one.
2. Restart the access function.
5
No access to EEPROM
1. Plug in the memory card.
a) During system start:
Start the fieldbus controller by switching the power
supply off and on.
b) In ongoing operation:
Restart the access function.
2. Should this error persist, contact I/O Support..
6
Backup function failed
1. Remove the memory card and remove the write
protection.
2. Plug the memory card back in.
3. Restart the access function.
4. If the error persists, replace the memory card with a
new one.
5. Restart the access function.
6. Should the error persist, contact I/O Support.
7
Restore function failed
1. Plug the memory card back in if the memory card has
been removed.
2. Close any existing FTP connection, establish a new
connection, and restart the access function.
3. Should the error persist, restart the device and the
access function.
4. If the error should persist, contact I/O Support.