![WAGO 750-880 Скачать руководство пользователя страница 182](http://html2.mh-extra.com/html/wago/750-880/750-880_manual_3156225182.webp)
182 Configuring via the Web-Based Management System (WBM)
WAGO-I/O-SYSTEM 750
750-880, 750-880/025-000 ETHERNET Programmable Fieldbus Controller
Manual
Version 1.0.1
10.10 Features
Use the "Features" HTML page to enable or disable additional functions.
Pos: 84.49 /Serie 750 (WAGO-I/O-SYSTEM)/Web-based Management-System/Seite Features/Features - Bild (750-880) @ 6\mod_1264772208300_21.doc @ 49050 @ @ 1
Figure 72: WBM page "Features"
Pos: 84.50 /Serie 750 (WAGO-I/O-SYSTEM)/Web-based Management-System/Seite Features/Features - Tabelle (750-880, -881) @ 6\mod_1265211909421_21.doc @ 49258 @ @ 1
Table 55: WBM page "Features"
Additional functions
Entry
Default
Description
enables an automatic software reset to be conducted
when a system error occurs
Autoreset on
system error
disables an automatic software reset to be conducted
when a system error occurs
Automatically set the static IP address enabled.
For this configuration, the fieldbus coupler/
controller uses a statically configured IP address if the
request via BootP fails.
BootP Request
before Static-IP
Automatically set the static IP address disabled.
For this configuration, the IP address request via BootP
is repeated in the event of error.
Pos: 84.51 /Serie 750 (WAGO-I/O-SYSTEM)/Web-based Management-System/Seite Features/Features - Tabelle (750-880 Ergänzung) @ 9\mod_1290522914211_21.doc @ 66770 @ @ 1