WAGO I/O System 750 XTR
Commissioning 87
750-677/040-000 4PWM 24 VDC 0.2A XTR
Manual
Version 1.0.0
The 750-333/040-000 fieldbus couplers allow channel pair granular
parameterization of the diagnostics as well as further module and channel or
channel pair specific settings. The following assignment applies to the
parameters of the I/O module, also in connection with the use of WAGO-I/O-
CHECK
or
e!
COCKPIT
.
Table 60: Device-Specific Parameters
GSD File
WAGO-I/O-
CHECK a
nd
e!COCKPIT
Description
Value
Selection Box
Value
I/O-module is
physically
plugged
*)
-
-
(optional) not plug fitted
-
Watchdog timer
[I/O module]
deactivated
Watchdog timer
[General]
Checkbox disabled
activated
*)
Checkbox enabled
*)
Diagnosis
[Channel pair x
(x = 0,1)]
disabled
*)
-
-
enabled
-
Bridge mode
[Channel pair x
(x = 1, 2)]
deactivated
*)
Bridge mode
[Channel x
(x = 1 & 2, 3 & 4)]
Checkbox disabled
*)
activated
Checkbox enabled
Load between
output and
[Channel x
(x = 0, 1, 2, 3)]
Uout
−
to CC 2 or CC6
*)
Load between output
and
[Channel x
(x = 1 & 2, 3 & 4)]
Uout
−
*)
Uout+ to CC 3 or CC7
Uout+
Operating mode
[Channel x
(x = 0, 1, 2, 3)]
PWM DC
*)
Operating mode
[Channel x
(x = 1 & 2, 3 & 4)]
PWM DC
PWM Frq
PWM Frq
Operating mode
[Channel x
(x = 0, 2)]
PWM Frq-Cnt
PWM Frq-Cnt
Pulse Frq-Cnt
Pulse Frq-Cnt
PWM Pulse-Dir
PWM Pulse-Dir
*)
Factory default