48 Operating Modes
WAGO I/O System 750 XTR
750-677/040-000 4PWM 24 VDC 0.2A XTR
Manual
Version 1.0.0
Table 31: Control Byte 2 (PWM Frq)
Control byte 2
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
RegCom
-
-
-
-
-
-
Enable DO 3 &
DO 4 Drivers
Legend
Enable DO 3 & DO 4
Drivers
0: The output driver for DO 3 & DO 4 is disabled.
1: The output driver for DO 3 & DO 4 is enabled.
RegCom
0: Register communication is switched off.
1: Register communication is switched on.
Control bytes 1 and 3 can be permanently “0” and have no influence on the
system.
Table 32: Status Byte 0 (PWM Frq)
Status byte 0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg
Com
General Error
Bit
Undervoltage
Short circuit
DO 1 or DO 2
-
-
-
Enable DO 1 &
DO 2 Drivers
Legend
Enable DO 1 & DO 2
Drivers
0: The status of the output driver for DO 1 & DO 2 is disabled.
1: The status of the output driver for DO 1 & DO 2 is enabled.
Short circuit DO 1 or
DO 2
0: There is no short circuit at outputs DO 1 or DO 2.
1: There is a short circuit at output DO 1 or DO 2.
Undervoltage
0: There is no undervoltage on the I/O module.
1: There is an undervoltage on the I/O module.
General Error Bit
0: There is no error.
1: There is an undervoltage or a short circuit.
Bits 0-3 are masked out.
RegCom
0: Register communication is disabled (normal mode).
1: Register communication is enabled.
Table 33: Status Byte 2 (PWM Frq)
Status byte 2
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reg
Com
General Error
Bit
Undervoltage
Short circuit
DO 3 or DO 4
-
-
-
Enable DO 3 &
DO 4 Drivers
Legend
Enable DO 3 & DO 4
Drivers
0: The status of the output driver for DO 3 & DO 4 is disabled.
1: The status of the output driver for DO 3 & DO 4 is enabled.
Short circuit DO 3 or
DO 4
0: There is no short circuit at outputs DO 3 or DO 4.
1: There is a short circuit at output DO 3 or DO 4.
Undervoltage
0: There is no undervoltage on the I/O module.
1: There is an undervoltage on the I/O module.
General Error Bit
0: There is no error.
1: There is an undervoltage or a short circuit.
Bits 0-3 are masked out.
RegCom
0: Register communication is disabled (normal mode).
1: Register communication is enabled.
Status byte 1 and 3 are permanently “0”.