64 Process Image
WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
Byte 1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
WARN
CAL OVER_1 OVER_2 OVER_3 OVER_4
STAT_SEL
WARN
Warning: Transient reaction measured value collection
active:
0 = OK
1 = the selected collection measured values are not
yet stable; a transient reaction must first
take place.
CAL
Indicates calibration mode:
0 = the I/O module is in measurement mode.
1 = the I/O module is in calibration mode.
OVER_1
Range limiting, process value 1:
0 = OK
1 = the measured value shown in process value 1
is situated outside the defined value range.
OVER_2
Range limiting, process value 2:
0 = OK
1 = the measured value shown in process value 2
is situated outside the defined value range.
OVER_3
Range limiting, process value 3:
0 = OK
1 = the measured value shown in process value 3
is situated outside the defined value range.
OVER_4
Range limiting, process value 4:
0 = OK
1 = the measured value shown in process value 4
is situated outside the defined value range.
STAT_SEL
Confirmation of the status messages requested in the output
data – status active for:
0 = status, phase L1
1 = status, phase L2
2 = status, phase L3
3 = status, I/O module