WAGO-I/O-SYSTEM 750 XTR
Appendix 297
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
Table 106: Parameter 25
Parameter 25 – Overvoltage Threshold Value Phase 3
Function
Data Type
Access
Factory Setting
Overvoltage threshold, phase 3,
Resolution: 0.1 V
UINT
R/W
0x1004 (410 V)
0:
The overvoltage threshold check is deactivated.
≥ 1
:
Value of the overvoltage threshold.
Table 107: Parameters 26 and 27
Parameters 26 and 27 – Overcurrent Threshold Value Phase 1
Function
Data Type
Access
Factory Setting
Overcurrent threshold value, phase 1
Resolution: 0.1 mA
UINT
R/W
0x0000C350
(5000 mA)
0:
The overvoltage threshold check is deactivated.
≥ 1:
Value of the overvoltage threshold check.
Table 108: Parameters 28 and 29
Parameters 28 and 29 – Overcurrent Threshold Value Phase 2
Function
Data Type
Access
Factory Setting
Overcurrent threshold value, phase 2
Resolution: 0.1 mA
UINT
R/W
0x0000C350
(5000 mA)
0:
The overvoltage threshold check is deactivated.
≥ 1
:
Value of the overvoltage threshold check.
Table 109: Parameters 30 and 31
Parameters 30 and 31 – Overcurrent Threshold Value Phase 3
Function
Data Type Access
Factory Setting
Overcurrent threshold value, phase 3
Resolution: 0.1 mA
UINT
R/W
0x0000C350
(5000 mA)
0:
The overvoltage threshold check is deactivated.
≥ 1
:
Value of the overvoltage threshold check.
Table 110: Parameters 32 and 33
Parameters 32 and 33 – Threshold Value Tamper Detect (Fault Current)
Function
Data Type Access
Factory Setting
Threshold value (peak value), Tamper Detect,
Resolution: 0.1 mA
UINT
R/W
0x0000000A
(1 mA)
≥ 0
:
Threshold value (peak value)