WAGO-I/O-SYSTEM 750 XTR
Connect Devices 143
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
Figure 35: Connection Schematic for Grounded Single-Phase Split-Phase Network for Power
Measurement for U
L1,
U
L2
> 400 V
RMS
and u
L1,
u
L2
≤
400 V
RMS
Table 42: Legend for Figure “Connection Schematic for Grounded Single-Phase Split-Phase Network
for Power Measurement for U
L1,
U
L2
> 400 V
RMS
and
u
L1,
u
L2
≤
400 V
RMS
”
No. Explanation
1 Generator:
Generator or transformer in single-phase split-phase connection, with
neutral conductor grounding
2 Current transformer (CT3) for current measurement in the neutral
conductor (optional)
3 Loads with impedances (Zx):
- Load connection: in split-phase connection
- Load type: all variants
4 Connection terminal N:
Reference potential for all voltage inputs and differential current inputs
5 Connection terminal L2:
Connection to the N connection (optional, to avoid erroneous measured
values for the unused phase)