WAGO-I/O-SYSTEM 750 XTR
Process Image 81
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
5.5.2
Collections 020, 021 and 022 – Harmonic Analysis
Wait for end of initialization time
The selected measured values of the collection stabilize after about 1100 ms.
If the upper harmonic that is to be analyzed (1 to 40) changes, it is necessary to
allow for an initialization time of 1100 ms for the measured values of the newly
selected upper harmonic.
Tabelle 29: Measured Values of Collections 020, 021 und 022 in the Process Image (PI)
MET_ID Measured Value
PI Data
Type
PI Scaling Factor
750-495/
040-000,
750-495/
040-002
750-495/
040-001
Harmonic Analysis on L1 (Collection 020)
001
RMS current, L1
UInt32
0.0001 A
0.0005 A
002
RMS voltage, L1
UInt32
0.01 V
0.01 V
003
Distortion, current, L1
UInt32
0.01 %
0.01 %
004
Distortion, voltage, L1
UInt32
0.01 %
0.01 %
100
Fundamental frequency
factor 1
depends on selected variable
1 … 40 Upper harmonic component L1
1st … 40th upper harmonic
depends on selected variable
Harmonic Analysis on L2 (Collection 021)
001
RMS current, L2
UInt32
0.0001 A
0.0005 A
002
RMS voltage, L2
UInt32
0.01 V
0.01 V
003
Distortion, current, L2
UInt32
0.01 %
0.01 %
004
Distortion, voltage, L2
UInt32
0.01 %
0.01 %
100
Fundamental frequency
factor L2
depends on selected variable
1 … 40 Upper harmonic component L2
1st … 40th upper harmonic
depends on selected variable
Harmonic Analysis on L3 (Collection 022)
001
RMS current, L3
UInt32
0.0001 A
0.0005 A
002
RMS voltage, L3
UInt32
0.01 V
0.01 V
003
Distortion, current, L3
UInt32
0.01 %
0.01 %
004
Distortion, voltage, L3
UInt32
0.01 %
0.01 %
100
Fundamental frequency factor
L3
depends on selected variable
1 … 40 Upper harmonic component L3
1st … 40th upper harmonic
depends on selected variable