66 Process Image
WAGO-I/O-SYSTEM 750 XTR
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
STAT2
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Clipping of current signal at Lx:
0 = OK
1 = the current signal is outside the measurable
range of the I/O module and has been
limited (clipped).
If STAT_SEL = status of I/O module:
- no significance
STAT1
If STAT_SEL = status of Lx = L1 / L2 / L3:
- Underrun of the ZC limit at Lx:
0 = OK
1 = greater measurement error due to
underrun of the required
input nominal voltage at Lx
If STAT_SEL = status of I/O module:
- no significance
Byte 3
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
COL_ID_SEL
COL_ID_SEL
Index of the selected measured value collection (see also
COL_ID in output data):
000 … 009 = -reserved-
010
= AC measured values
011 … 019 = -reserved-
020
= harmonic analysis, L1
021
= harmonic analysis, L2
022
= harmonic analysis, L3
023 … 255 = -reserved-