DeviceNet • 97
Configuration / Parametering with the Object Model
WAGO-I/O-SYSTEM 750
DeviceNet
4.6.2.1.13 Module
Configuration (0x80):
Instance 0:
Attribute
ID
Used in
buscoupler
Access
rule
Name Data
type
Description
Value
1
required
get
Revision
UINT
Revision of this Object.
1 (0x0001)
2 optional
get
Max
instance
UINT
maximum number of instances
-
Description of the instances:
Instance ID
Description
1
reference to the first analog module (coupler/controller)
2
reference to the next connected module (I/O module)
...
16
reference to the last possible connected module (I/O module)
Instance 1 to 65:
Attribute
ID
Used in
buscoupler
Access
rule
Name Data
type
Description
Value
1
dep. on kind
of connected
modules
get ModulDe-
scription
WORD
Description of the connected
modules
(Instance 1 = Coupler/Controller,
Instance 2 = Module 1,...)
Bit 0: Module with inputs,
Bit 1: Module with outputs,
Bit 8-14: Data width internal in
bits
Bit 15: 0/1 Analog/Digital module,
For analog modules the bits 1-14
describe the type of module i. e.
460 for the module 750-460
actual
output
value
Services:
Service Code
Service Name
Description
0x0E
Get_Attribute_Single
Used to read a DeviceNet Object attribute
value