DeviceNet • 89
Configuration / Parametering with the Object Model
WAGO-I/O-SYSTEM 750
DeviceNet
ut_action
13 required
get pro-
duced_con
nec-
tion_path_
length
UINT
number of Bytes in pro-
duced_connection_path attribute
14 required
get/set
pro-
duced_con
nec-
tion_path
Array of
USINT
specifies the application objects which data is
to be produced by this connection object
15 required
get con-
sumed_co
nnec-
tion_path_
length
UINT
number of Bytes in con-
sumed_connection_path attribute
16 required
get con-
sumed_co
nnec-
tion_path
Array of
USINT
specifies the application objects that are to
receive the data consumed by this connection
object
17 required
get/set
produc-
tion_inhibi
t_time
USINT
defines minimum time between new data
production
Services:
Service Code
Service Name
Description
0x0E
Get_Attribute_Single
Used to read a DeviceNet Object attribute value
0x10 Set_Attribute_Single
Used
to
modify a DeviceNet object attribute value
0x05
Reset
Restores connection default values.
The instances are not available if the connection is in state „non existent“.
I/O Connection Object State
Non-Existent
Delete from any state
Get_Atribute/Set_Attribute
Get_Atribute/
Set_Attribute/
Apply_Attributes
Get_Atribute/
Set_Attribute/
Apply_Attributes/
Reset/Message
Produced/Consumed
Apply Atributes
Apply_Atributes
Apply_Atributes
Create
Delete
Reset
Inactivity/Watchdog
Timeout & watchdog_timeout_action =
Transition to Time Out
Configuring
Established
Timed Out
Waiting for
Connection ID
Fig. 4-1: Status of I/O Connection Objects
g012546x