Fieldbus Coupler • 67
Fieldbus Coupler 750-346
WAGO-I/O-SYSTEM 750
DeviceNet
3.1.9 Technical Data
System data
Max. no. of nodes
64 with scanner
Max. no. of I/O points
ca. 6000 (depends on master)
Transmission medium
shielded Cu cable,
trunk line: AWG 15, 18 (2x 0.82mm
2
+2x1.7mm
2
)
drop line: AWG 22, 24 (2x0.2mm
2
+2x0.32mm
2
)
Max. length of bus line
100 m ... 500 m
(depends on baud rate / on the cable)
Baud rate
125 kBaud, 250 kBaud, 500 kBaud
Buscoupler connection
5-pole male connector, series 231 (MCS)
female connector 231-305/010-000/050-000
is included
Standards and approvals
UL
E175199, UL508
DEMKO
02 ATEX 132273 X
II 3 GD EEx nA II T4
Conformity marking
CE
Accessories
EDS files
Download: www.wago.com
Miniature WSB quick marking system
Technical data
Max. number of I/O modules
64
Fieldbus
Input process image
Output process image
max. 32 Byte
max. 32 Byte
Configuration
via PC or PLC
Voltage supply
DC 24 V (-15 % / + 20 %)
Current consumption
- via power supply terminal
typ.
at no-
minal load
260 mA at 24 V
- via DeviceNet interface
<120 mA at 11 V
Efficiency of the power supply
typ.
at
nominal load
80 %
Internal current consumption
350 mA at 5 V
Total current for I/O modules
650 mA at 5 V
Dimensions (mm) W x H x L
50 x 65* x 97
(*from top edge of mounting rail)
Weight ca.
120
g
EMC interference resistance
gem. EN 61000-6-2 (2)
EMC interference transmission
gem. EN 50081-2 (94)