94 • DeviceNet
Configuration / Parametering with the Object Model
WAGO-I/O-SYSTEM
750
DeviceNet
0xFFFF(default): ConsumedConnectionSize
corresponds to the data width of the con-
nected output modules 0 – 32 ( PI_LIMIT ):
Fixed width of the ConsumedConnectionSize,
independent of the output modules.
PI_LIMIT – 0xFFFE: These values These
values cannot be set and led to fault messages.
The adjusted value become only on valid with
next switching.
50 specific
get/set
reserved
UINT
0xFFFF
51 specific
get/set
BK_FBC_CF
G
UINT
Defines configuration settings
Bit 0: =1 switches off global the announce-
ment of active diagnostic messages via the
MS LED. The diagnostic messages are trans-
ferred however further over the fieldbus. A
change of this attitude becomes only active
after a PowerOn cycle.
Bit 1..15 reserved.
Services:
Service Code
Service Name
Description
0x0E
Get_Attribute_Single
Used to read a DeviceNet Object attribute
value
0x10 Set_Attribute_Single Used
to
modify a DeviceNet object attribute
value
4.6.2.1.9 Discrete Input Point Object (0x65):
Instance 0:
Attribute
ID
Used in
buscoupler
Access
rule
Name Data
type
Description
Value
1
required
get
Revision
UINT
Revision of the Discrete Input
Point Object, Range 1-65535, class
definition upon which the imple-
mentation is based.
0x01
2 optional
get
Max
instance
UINT
maximum number of instances of
an object currently created in this
class level of the device
0x00ff
Description of the instances:
Instance ID
Description
1
Reference to the first digital input point
2
Reference to the next digital input point
...
255
Reference to the last possible digital input point
Instance 1 to 255:
Attribute
ID
Used in
buscoupler
Access
rule
Name Data
type
Description
Value
1
dep. on kind
of connected
modules
get DIPOBJ_
VALUE
BIT
digital input bit
0:off
1:on
Services:
Service Code
Service Name
Description
0x0E
Get_Attribute_Single
Used to read an object attribute value.