Fieldbus Coupler • 53
Fieldbus Coupler 750-346
WAGO-I/O-SYSTEM 750
DeviceNet
Example for static assembly (default assembly):
The default assembly is:
Output1
(I/O Assembly Instance 1)
Input1
(I/O Assembly Instance 4)
In this example, the fieldbus node arrangement looks like this:
1) 1 ECO fieldbus coupler DeviceNet (750-346),
2) 1 digital 4-channel input modules (i. e. 750-402),
3) 1 digital 4- channel output module (i. e. 750-504),
4) 1 analog 2- channel output module with 2 bytes per channel
(i. e. 750-552),
5) 1 analog 2- channel input module with 2 bytes per channel
(i. e. 750-456),
6) 1 End module (750-600).
Input process image:
Default process data, input image (Assembly Class, Instance 4)
Byte
.7
.6
.5
.4
.3
.2
.1
.0
0
low byte channel 1
1
high byte channel 1
2
low byte channel 2
3
high byte channel 2
4
not used
DI04
1)
DI03
1)
DI02
1)
DI01
1)
5
CS08
2)
CS07
2)
CS06
2)
CS05
2)
CS04
2)
CS03
2)
CS02
2)
CS01
2)
1)
DI = = Digital Input
2)
CS = Coupler Status (The last byte in the input process image is the Status Byte
of the Coupler, CS01...CS08, see also Object 0x64, Instance 1, Attribute 5)
CS01 =1: internal bus error (0x01)
CS02 =1: module communication error (0x02)
CS04 =1: module diagnostic (0x08)
CS08 =1: fieldbus error (0x80)
Output process image:
Default process data, output image (Assembly Class, Instance 1)
Byte
.7
.6
.5
.4
.3
.2
.1
.0
0
low byte channel 1
1
high byte channel 1
2
low byte channel 2
3
high byte channel 2
4
not used
DO04
1)
DO03
1)
DO02
1)
DO01
1)
1)
DO = Digital Output