82 • DeviceNet
Configuration / Parametering with the Object Model
WAGO-I/O-SYSTEM
750
DeviceNet
4.6.2.1.3 Message Router (0x02):
no attribute, no services
4.6.2.1.4 DeviceNet Object (0x03):
Instance 0:
Attribute
ID
Used in
buscoupler
Access
rule
Name Data
type
Description
Default
Value
1 required
get
Revision
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation
is based.
0x02
Instance 1:
Attribute
ID
Used in
buscoupler
Access
rule
Name Data
type
Description
Default
Value
1
Optional
get/set
MAC ID
USINT
Node address
0 - 63
2
Optional
get
Baud Rate USINT
Baud rate
0 - 2
3
Optional get/set BOI BOOL Bus-off
Interrupt
0/1
4
Optional get/set Bus-Off
Counter
USINT
Number of times CAN went to
the bus-off state
0 - 255
5 Optional
get
Allocation
Informa-
tion
Allocation
Choice
Byte
Master`s
ID
Struct of:
BYTE,
USINT
s. MAC ID of Master (from
Allocate)
0 - 63, 255
Services:
Service Code
Service Name
Description
0x0E
Get_Attribute_Single
Used to read a DeviceNet Object attribute value
0x10 Set_Attribute_Single Used
to
modify a DeviceNet object attribute value
0x4B Allocate_Master/Slave_Connection
Requests
the use of the predefined Master/Slave
connection
0x4C Release_Group_2_Identifier_Set
Indicates
that the specified connections within the
predefined Master/Slave connection set are no
longer desired. These connections are to be released
(deleted)