118 •
I/O
Modules
WAGO-I/O-SYSTEM
750
DeviceNet
Serial Interface Modules with Standard Data Format
750-650/000-001, -014, -015, -016
750-651/000-001
750-653/000-001, -006
The above Serial Interface Modules with Standard Data Format have a total of
6 bytes of user data in both the Input and Output Process Image (5 bytes of se-
rial data and 1 byte of control/status). The following table illustrates the Input
and Output Process Image, which have a total of 6 bytes mapped into each im-
age.
Input and Output Process Image
Instance
Byte Destination
Remark
C/S Control/Status
byte
D0
D1
D2
D3
n
D4
Data bytes
The specialty modules represent 1x6 bytes input and output data and seize 1
Instance in Class (0x67) and 1 Instance in Class (0x68).
Data Exchange Module
750-654, (and the variation /000-001)
The Data Exchange modules have a total of 4 bytes of user data in both the In-
put and Output Process Image. The following tables illustrate the Input and
Output Process Image, which has a total of 4 bytes mapped into each image.
Input and Output Process Image
Instance
Byte Destination
Remark
D0
n
D1
D2
n+1
D3
Data bytes
The specialty modules represent 2x2 bytes input and output data and seize 2
Instances in Class (0x67) and 2 Instances in Class (0x68).
SSI Transmitter Interface Modules
750-630 (and the variations /000-001, -002, -006, -008, -009, -011, -012,
-013)
The above SSI Transmitter Interface modules have a total of 4 bytes of user
data in the Input Process Image, which has 4 bytes mapped into the image.