92 • DeviceNet
Configuration / Parametering with the Object Model
WAGO-I/O-SYSTEM
750
DeviceNet
LL_C_PAT
H
used to hold an enumerator for the assembly
path and the class and instance for modules
object (discrete input point ...) paths. Write
only instance values that are available for
couplers present module configuration (e.g.
do not use analog input points if only digital
modules are fixed to the coupler.
14 specific
get/set
BK_SEL_S
TORED_CO
SCYC_C_P
ATH
UINT
Non volatile power up value for the change of
state and cyclic connection path. The attribute
is used to hold an enumerator for the assem-
bly path and the class and instance for mod-
ules object (discrete input point...) paths.
Write only instance values that are available
for couplers present module configuration (e.g
not use analog input points if only digital
modules are fixed to the coupler.)
4:analog and digital input data plus Status,
5: digital input data plus Status,
6: analog input data plus Status,
7:analog and digital input data,
8:digital input data
9: analog input data,
12: analog and digital input data plus
BK_LED_ERR_CODE (C 100, I 1, A45)
13: analog and digital input data plus
BK_LED_ERR_CODE (C 100, I 1, A45) plus
BK_LED_ERR_ARG (C 100, I 1, A46)
14: analog and digital input data plus
BK_LED_ERR_CODE (C 100, I 1, A45) plus
BK_LED_ERR_ARG (C 100, I 1, A46) plus
Status (C 100, I 1 A 5) plus DNS_i_Trmnldia
(C 100, I 1, A6) plus BK_DIAG_VALUE
(C 100, I 1, A47)
15: Status (C 100, I 1 A 5) plus three bytes,
which are always zero plus analog and digital
input data
15 specific
get/set
BK_EM_ex
pected_pac
ket_rate
UINT
Defines the default timing associated with
this Explicit Messaging Connection
16 specific
get/set
BK_EM_wa
tchdog_tim
eout_action
USINT
Defines how to handle Inactivity/Watchdog
Explicit Messaging Connection timeouts
17 specific
get/set
BK_PIO_ex
pected_pac
ket_rate
UINT
Defines the default timing associated with
this Poll I/O Connection Connection
18 specific
get/set
BK_PIO_w
atch-
dog_timeou
t_action
USINT
Defines how to handle Inactivity/Watchdog
Poll I/O Connection Connection timeouts
19 specific
get/set
BK_BS_ex
pected_pac
ket_rate
UINT
Defines the default timing associated with
this Bit–Strobe I/O Connection Connection
20 specific
get/set
BK_BS_wa
tchdog_tim
eout_action
USINT
Defines how to handle Inactivity/Watchdog
Bit–Strobe I/O Connection Connection time-
outs
21 specific
get/set
BK_COS_e
xpected_pa
cket_rate
UINT
Defines the default timing associated with
this Change of State and Cyclic I/O Connec-
tion
22 specific
get/set
BK_COS_
watch-
dog_timeou
t_action
USINT
Defines how to handle Inactivity/Watchdog
Change of State and Cyclic I/O Connection
timeouts
23 specific
get/set
BK_BOI
USINT
Defines the default value for BOI(Obj0x3
Inst. 1 Att. 3. It handles the CAN Bus-Off
situation.
0: Hold the CAN chip in its bus-off (reset)
state upon detection of a bus-off indication
1: If possible, fully reset the CAN chip and
continue communicating upon detectionof a
bus-off indication
24 specific
get/set
BK_DO_FA
ULT_REAC
TION_ON_
USINT
Defines the behavior after de allocation the
polled I/O connection
0: (default) do nothing