3-Phase Power Measurement Module, 1 A
Register Address
Measured Variable
Measure-
ment Unit 1
A, 5 A / Ro-
gowski
Register Ac-
cess
Update Rate
[ms]
0x00A4
Active Energy L3
Wh
1)
/kWh
R
1100
0x00A6
Active Energy import L3
Wh
1)
/kWh
R/W
1100
0x00A8
Active Energy export L3
Wh
1)
/kWh
R/W
1100
0x00AA
Reactive Energy L3
varh
2)
/kvarh
R
1100
0x00AC
Reactive Energy inductive L3
varh
2)
/kvarh
R/W
1100
0x00AE
Reactive Energy capacitive L3
varh
2)
/kvarh
R/W
1100
0x00B0
Apparent Energy L3
VAh
3)
/kVAh
R/W
1100
0x00B2
Active Energy total
Wh
1)
/kWh
R
1100
0x00B4
Active Energy import total
Wh
1)
/kWh
R
1100
0x00B6
Active Energy export total
Wh
1)
/kWh
R
1100
0x00B8
Reactive Energy total
varh
2)
/kvarh
R
1100
0x00BA
Reactive Energy inductive total
varh
2)
/kvarh
R
1100
0x00BC
Reactive Energy capacitive total
varh
2)
/kvarh
R
1100
0x00BE
Peak Value Voltage U
Lx−N
,
for one phase
V
R
40
0x00C0
Peak Value Current I
Lx
,
for one phase
A
R
40
0x00C2
RMS Current fundamental cmpt.
A
R
40
0x00C4
RMS Voltage fundamental cmpt.
V
R
40
0x00C6
RMS Current upper harmonic A
A
R
40
0x00C8
RMS Current upper harmonic B
A
R
40
0x00CA
RMS Current upper harmonic C
A
R
40
0x00CC
RMS Voltage upper harmonic A
V
R
40
0x00CE
RMS Voltage upper harmonic B
V
R
40
0x00D0
RMS Voltage upper harmonic C
V
R
40
0x00D2
Distortion Factor THD Current
%
R
40
0x00D4
Distortion Factor THD Voltage
%
R
40
0x00D6
HD Current upper harmonic A
%
R
40
0x00D8
HD Current upper harmonic B
%
R
40
0x00DA
HD Current upper harmonic C
%
R
40
0x00DC
HD Voltage upper harmonic A
%
R
40
0x00DE
HD Voltage upper harmonic B
%
R
40
0x00E0
HD Voltage upper harmonic C
%
R
40
0x00E2
Power Factor PF Total
–
R
40
1)
FW version 3.0 or higher: kWh
2)
FW version 3.0 or higher: kvarh
3)
FW version 3.0 or higher: kVAh