2857-570/024-001
Functions
38
Product manual | Version: 2.0.0
3-Phase Power Measurement Module, 1 A
2. Create a new project. Click
[File> New]
.
ð
The
Target Settings
dialog appears.
3. Under
Configuration
, select the hardware you are using.
4. Click the
[OK]
button
ð
The
New POU
dialog appears.
5. Click the
[Cancel]
button because you do not want to create a new module.
6. In the main menu, select the
[Resources]
tab.
7. In the directory, select the
[PLC Configuration]
entry.
ð
The
PLC Configuration
workspace appears.
8. In the tree structure, select the entry
[Modbus-Master(FIX)].
.
ð
The tab
MODBUS Master configurator
opens.
9. Click the
[Network view]
button.
ð
The dialog
MODBUS Master configurator
opens.
10. Right-click the entry
MODBUS master
and select
[Add Serial Interface]
.
11. The
Settings: Serial Interface
dialog opens.
12. Select the setting
"19200"
in the
Baud rate
selection box.
13. Select the setting
"Even"
in the
Parity
selection box.
14. Click the
[OK]
button.
ð
The entry
Interface (COM2)
is created in the MODBUS master configurator dia-
log.
15. Right-click the entry
Interface (COM2)
and select
[Add Modbus Slave]
.
ð
The dialog
MODBUS slave selection
opens.
16. Double-click the entry
[Generic MODBUS slave]
.
ð
The entry is displayed in the
Choosen devices
area.
17. Click the
[OK]
button.
ð
The entry
Modbus slave
is created in the MODBUS master configurator dialog.
18. Right-click the
Communication
input field; select
[Edit]
.
ð
The
Communication settings
dialog opens.
19. Enter the value "1" in the
Modbus unit ID
input field.
20. Click the
[OK]
button.
ð
The entry
Generic Variables
is created in the MODBUS master configurator dia-
log.
21. Right-click the entry
Generic Variables
and select
[Add]
.
ð
A new variable is created in the MODBUS master configurator dialog.
22. Right-click the entry
Generic Variables
and select
[Add]
.
ð
The new variable
xNewVar
is created in the MODBUS master configurator dialog.
23. Double-click the variable
[xNewVar]
.
24. Rename the variable tp
"rVoltageL1"
.
25. Click the input field
[Type > REAL]
.