Technical Description
TITANUS
SUPER·SENS
®
2
– 10
Data: 02/09
TSS_02_A-en-e
2.2.3 Diagnostic tool DIAG+
TITANUS
SUPER · SENS
®
infrared-LED
diagnostic device
battery case
connection cable
for PC
connection cable
diagnostic interface
(pre-fabricated cable)
DIAG+
3.5"-disks with
evaluation software
3.5"-disks with
evaluation software
receiving diode
Fig. 2.7: Diagnostic device to read out the state of the device
For maintenance and service the diagnostic device is able to limit the
number of faults (refer to
6H
Fig. 2.7). The current and memorized state of
the device is read out through data transmission on optical basis.
TITANUS
®
has an infrared-LED that continuously sends data.
TITANUS
®
memorizes set faults and resets for at least 96 hours, even if
the cause of the fault has already been eliminated. This allows to analyze
even shortly, sporadically occurring environmental influences (e.g.
changed operating conditions).
By means of the diagnostic device the smoke level and the air flow can
be recorded.
At the bottom side of the diagnostic device there is the receiving diode. In
order to receive the data the diagnostic device has to be put on the infra-
red-LED of TITANUS
®
. Via a micro-processor in the diagnostic device the
information sent by the air sampling smoke detection system are re-
ceived and memorized. Through a serial interface cable the memorized
data are directly passed to a PC
2F
3
. The data remain in the diagnostic de-
vice until another air sampling smoke detection system is analyzed. The
evaluation and the display are effected by means of the delivered soft-
ware.
3
PC with serial interface (COM1 or COM2) and WINDOWS95
Содержание TITANUS SUPER-SENS
Страница 2: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 4: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 10: ...TITANUS SUPER SENS Contents TSS_inhalt en e Data 02 09 www acornfiresecurity com www acornfiresecurity com ...
Страница 14: ...General TITANUS SUPER SENS 0 4 Data 02 09 TSS_00_A en e www acornfiresecurity com www acornfiresecurity com ...
Страница 126: ...Installation TITANUS SUPER SENS 5 34 Data 02 09 TSS_05_B en e www acornfiresecurity com www acornfiresecurity com ...
Страница 154: ...Commissioning TITANUS SUPER SENS 7 10 Data 02 09 TSS_07_A en e www acornfiresecurity com www acornfiresecurity com ...
Страница 164: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 172: ...www acornfiresecurity com www acornfiresecurity com ...