TITANUS
SUPER·SENS
®
Pipe
Design
TSS_04_A-en-e
Data: 02/09
4 –
39
If it is absolutely necessary to attach the pipe system directly behind baf-
fles, sound suppressers or angles, the main flow speed areas will have to
be monitored (see Fig. 4.22/23).
Fig. 4.22: Change in direction of a duct without baffles
sound absorption
main speed area
hole
air sampling pipe
air conditioning duct
Fig. 4.23: Sound suppressors in a duct
The following must be taken into consideration when installing a pipe sys-
tem in air conditioning ducts:
•
Air recirculation (see following page) should be planned for, since
the TITANUS
®
and the pipe system are located in different pressure
areas.
•
The pipe inlets in the duct must be sealed so that they are air tight.
•
The part of the pipe system located outside of the duct must be
sealed so as to be air tight.
Содержание TITANUS SUPER-SENS
Страница 2: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 4: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 10: ...TITANUS SUPER SENS Contents TSS_inhalt en e Data 02 09 www acornfiresecurity com www acornfiresecurity com ...
Страница 14: ...General TITANUS SUPER SENS 0 4 Data 02 09 TSS_00_A en e www acornfiresecurity com www acornfiresecurity com ...
Страница 126: ...Installation TITANUS SUPER SENS 5 34 Data 02 09 TSS_05_B en e www acornfiresecurity com www acornfiresecurity com ...
Страница 154: ...Commissioning TITANUS SUPER SENS 7 10 Data 02 09 TSS_07_A en e www acornfiresecurity com www acornfiresecurity com ...
Страница 164: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 172: ...www acornfiresecurity com www acornfiresecurity com ...