8.4 Changing the air filter LF-AD –x
1
2
prim ary filter
coarse dust filter
Fine dust filter
air sampling pipe
Air fl
ow d
irec
tion
air filter for
Adx and TITANUS,
type LF-AD
Fig. 8.3: change the filter inserts
To clean or change the filter inserts, carry out the following steps (see fig.
8.4):
1
Loosen the four screws and remove the housing lid.
2
Remove the filter inserts and check how soiled they are. The inserts
can be cleaned if there is a small amount of soiling and must be re-
placed if soiling is heavy.
3
Carefully clean the inside of the housing from any dust. Replace the
cleaned or replaced filter inserts in the correct sequence, which is
shown on the instruction label of the housing floor.
4
Replace and screw down the housing lid.
In environments with a high level of fine-grade dust, three optional fine
dust filters can be used in addition.
Opening the housing lid of the air filter LF-AD-x causes an air flow fault
in TITANUS
®
.
TIP
INSTRUCTION
Содержание TITANUS SUPER-SENS
Страница 2: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 4: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 10: ...TITANUS SUPER SENS Contents TSS_inhalt en e Data 02 09 www acornfiresecurity com www acornfiresecurity com ...
Страница 14: ...General TITANUS SUPER SENS 0 4 Data 02 09 TSS_00_A en e www acornfiresecurity com www acornfiresecurity com ...
Страница 126: ...Installation TITANUS SUPER SENS 5 34 Data 02 09 TSS_05_B en e www acornfiresecurity com www acornfiresecurity com ...
Страница 154: ...Commissioning TITANUS SUPER SENS 7 10 Data 02 09 TSS_07_A en e www acornfiresecurity com www acornfiresecurity com ...
Страница 164: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 172: ...www acornfiresecurity com www acornfiresecurity com ...