TITANUS
SUPER·SENS
®
Product
Description
TSS_01_A-en-e
Data: 02/09
1
– 1
1
Product
Description
1.1
Characteristics
of
TITANUS SUPER·SENS
®
TITANUS
SUPER · SENS
®
is the latest generation of the well-proven
WAGNER-air sampling smoke detection systems. As highly sensitive
device TITANUS
SUPER · SENS
®
reaches a detection quality not known
so far. In particular, it can be used for room monitoring in case of high
value concentration and to control climatic cabinets or climatic ducts in
case of high air exchange rates. TITANUS
SUPER·SENS
®
can even be
used in critical areas such as EDP-rooms.
High
Sensitivity
The device has a display sensitivity of 0.0025%/m light obscuration.
According to the application further sensitivities can be set at the base
board. Thus, a large detection range throughout all typical standard fire
types is possible.
Network
System
By means of an optional network board several TITANUS
SUPER·SENS
®
can be connected to form a network. Through a central
network unit the operator can monitor the whole installation as far as
smoke level, air flow values etc. are concerned.
Diagnostic
Device
The diagnostic device permits a quick and reliable fault localization for
maintenance and service. The reading out of the current device state is
effected by means of an optical data transmission.
Safe Air Flow Monitoring
Like point-type detectors, which are electronically monitored to detect line
fractures and short circuits, air sampling systems require a complex and
safe air flow monitoring. The unique air flow sensor technology used in all
WAGNER-air sampling systems guarantees the detection of faults such
as pipe fracture or blockage of single air sampling points.
The air flow monitoring is temperature compensated and can be
independent of the air pressure.
Patented Air Sampling
Points
Depending on the required project planning the air sampling points have
defined drill hole diameters. For these exact air sampling points
WAGNER has developed patented
aspiration-reducing film sheets
with marking tapes and clips that permit an easy mounting and avoid
secondary noise e.g. „whistling“.
Temperature
Range
TITANUS
SUPER·SENS
®
can be operated in a temperature range
between -20°C and +60°C. Thus, in contrast to conventional highly
sensitive early smoke detection systems operation below 0°C is possible
for the first time.
Содержание TITANUS SUPER-SENS
Страница 2: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 4: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 10: ...TITANUS SUPER SENS Contents TSS_inhalt en e Data 02 09 www acornfiresecurity com www acornfiresecurity com ...
Страница 14: ...General TITANUS SUPER SENS 0 4 Data 02 09 TSS_00_A en e www acornfiresecurity com www acornfiresecurity com ...
Страница 126: ...Installation TITANUS SUPER SENS 5 34 Data 02 09 TSS_05_B en e www acornfiresecurity com www acornfiresecurity com ...
Страница 154: ...Commissioning TITANUS SUPER SENS 7 10 Data 02 09 TSS_07_A en e www acornfiresecurity com www acornfiresecurity com ...
Страница 164: ...www acornfiresecurity com www acornfiresecurity com ...
Страница 172: ...www acornfiresecurity com www acornfiresecurity com ...