Commissioning
TITANUS
RACK·SENS
®
1U
7
– 6
Data: 03/09
TRS_A_07-en-e
The green operation mode indicator will flash while the TITANUS
RACK·SENS
®
1U
is initialising. If initialisation is completed, the operation
mode indicator will light up continuously.
Air flow initialisation can take up to 2 hours. It is successfully completed
when a constant air flow has been attained in the TITANUS
RACK·SENS
®
1U
The air flow in the TITANUS
RACK·SENS
®
1U should not be altered dur-
ing the initialisation phase.
In a normal situation the TITANUS
RACK·SENS
®
1U
should now run
without any problems. If this is not the case, follow the procedures de-
scribed in section 8.2 (Procedure in the event of a fault).
4. If no faults or alarms are shown on the TITANUS
RACK·SENS
®
1U
display, you can now switch the key-operated switch on the front of
the TITANUS
RACK·SENS
®
1U
device to the “On” position.
5. The device is now ready for operation and is no longer isolated from
the fire alarm line. Alarms and fault signals will now be forwarded to
an optional associated fire alarm system. Likewise in the event of an
alarm, an optionally connected relay (via shutdown module) will be
energised for electrical shutdown and, if not blocked/inhibited by an
door contact, an optionally connected extinguishing systems will be
activated.
button
Fig. 7.3: Air flow initialisation
INSTRUCTION