TITANUS
RACK·SENS
®
1U
Maintenance
TRS_A_08-en-e
Data: 03/09
8
– 1
8
Maintenance
8.1 Procedure for servicing
If servicing or an inspection is carried out on the TITANUS
RACK·SENS
®
1U device, the key-operated switch on the front of the TITANUS
RACK·SENS
®
1U device should be switched to the “Service” position
within 10 seconds for a system with monitored cabinet doors. If not, a
fault will be released.
In the “Service” setting, forwarding of alarms and fault signals as well as
any optional associated shutdown or fire alarm system will be disabled.
Before the TITANUS
RACK·SENS
®
is switched to the “On” operating
mode again, alarms or faults must no longer be present as otherwise
shutdown will be set off immediately after changing the switch position.
ATTENTION