Commissioning
TITANUS
RACK·SENS
®
1U
7
– 2
Data: 03/09
TRS_A_07-en-e
Removing active modules (i.e. extinguishing-shutdown modules) will u-
sually lead to a reduced functionality of the fire protection system and
possibly to a loss of fire protection altogether.
A defective module must be replaced immediately.
A defective module can be removed from the system configuration by us-
ing the „Config.“ button as follows:
-
Put the key switch in position „Service“.
-
Press „Config.“ button for 10 seconds.
The device will perform a LED- and buzzer test. System configuration
mode is indicated by the service / blocked and fault LED-symbols
which are flashing simultaneously.
If the optional temperature module is installed, the associated display
will show in this special case the number of connected extinguishing-
/shutdown modules. Regardless of the presence availability of the
temperature module, the device will be now in configuration mode.
-
By pressing again the „Config.“ button for another 10 seconds, the
actual system configuration will be updated and stored. The device is
confirming the update with three beeps by the internal buzzer. The
service/blocked indicator will stop flashing and be continuously on.
-
Alternatively by pressing the „Reset“ button or by putting the key-
switch into the “ON” position, the actual system configuration will be
ignored. In this case the device will show a fault when switched to the
„On“ position since the defective module was not removed from the
system configuration.
Display of connected temperature sensors and modules is only available
with an installed temperature module. Removing modules from the sys-
tem configuration is still possible without this temperature module, but
displaying the number of connected modules is not available.
An actual system configuration can be checked via the diagnostics tool
DIAG 3.
7.1.3 Reset and buzzer off button
This button enables alarms and faults to be reset when the TITANUS
RACK·SENS
®
1U device is in service mode if the event which caused it
is no longer present. To do so, the key switch must be switched to the
“Service” position and the “Config.” button be held down for about 3 seco-
nds.
In normal operating mode the TITANUS
RACK·SENS
®
1U
internal buzzer
can be switched off using this switch. The buzzer will come back on for
each new fault or each new alarm which occurs. The buzzer is reset by
pressing the button.
ATTENTION
INSTRUCTION