Carry out all circuit wiring work with the device fully disconnected!
Alarm, pre-alarm, service/blocked, release and fault contacts an be used
for purposes such as connection to a fire alarm system or activation of
signal devices and building management systems.
Name Type
Potential-free
contact
Description
Service/blk. Output
yes
NC
Alarm 1
Output
yes
NO
Alarm 2
Output
yes
NO
Pre Alarm 1
Output
yes
NO
Pre Alarm 2
Output
yes
NO
Fault Output yes
NC
Reset
Input
no
To be connected to
external, potential
free contact (NO).
Reset will occur on
closed contact.
24 V / 0 V
Output
no
Supply for ext.
bus modules
Data A/B
Output
no
Data bus for ext.
bus modules
Door Switch
Input
no
To be connected to
external, potential
free door contact
(NO, door open)
Man. Release
Input
no
Expects 4.7 k
Ω
for
operation and
1 k
Ω
for release
Released Output
yes NO
Temp. 1
Temp. 2
Temp. 3
Temp. 4
Temp. 5
Input
Input
Input
Input
Input
no
no
no
no
no
Expects 10 k
Ω
NTC temperature
sensor (default)
Relais 1
Relais 2
Relais 3
Relais 4
Relais 5
Output
Output
Output
Output
Output
yes
yes
yes
yes
yes
NO
NO
NO
NO
NO
ATTENTION