Commissioning
TITANUS
RACK·SENS
®
1U
7
– 8
Data: 03/09
TRS_A_07-en-e
7.2.4 Settings for main board and detector module
All TITANUS
RACK·SENS
®
1U
settings are made using the diagnostics
tool. Diagnostics tool installation and usage are described in more detail
in section 7.9.
Pressing the “Settings” button enables you to access the screen where
you can change individual settings. Pressing the “Accept” button stores
the new settings in the TITANUS
RACK·SENS
®
1U
device. Pressing the
“Default” button re-establishes the default settings.
TITANUS RACK·SENS
® -
00000
Set
m
hPa
V
%/m
s
%
min
%
%/m
%
s
0
30
1
0
40
0.500
60
0.500
60
0
1013
9,0
s
File
Record
Settings
Device-Selection
More
?
Bus elements B
Smoke level
Events
Settings A
Settings B
Status
Bus elements A
(Date , Time)
Detectore module 1
Buzzer
Fault latched
Dynamic air flow
Height above sea level
Air pressure
Fan voltage
Action alarm threshold
Sensitivity (Fire alarm)
Detector module 2
Pre- warning time
Alarm delay
Air flow range
Fault delay
Airflow init
Mainboard
Reception
Serial No.
Action alarm threshold
Sensitivity (Fire alarm)
Set
Active initialisation
Fig. 7.5: Settings for sensitivity, alarm delay, air flow range and fault delay