TITANUS
RACK·SENS
®
1U
Design
TRS_A_04-en-e
Data: 03/09
4 –
19
4.4.3
Pipe
Design
4.4.3.1
Simplified Pipe Design (local application protection)
Simplified project planning is used for equipment protection.
4.4.3.2 I-Pipe
system
1 Pipe system
TITANUS
RACK·SENS
®
1U
P
d
TITANUS
RACK·SENS
®
Fig. 4.13: I-pipe system, e.g. for equipment protection
Limit values
min. distance
TITANUS
P
®
P
– 1
st
aspiration hole
0,2 m
max. distance
TITANUS
P
®
P
– 1
st
aspiration hole
10 m
max. pipe length per pipe system
pipe
∅
25 mm
in addition to the pipe
∅
12 mm
15 m
8 x 3 m
max. number aspiration holes (n)
per pipe system
10
maximum distance
between the aspiration holes (d)
0,1 m
minimum distance
between the aspiration holes (d)
4 m
Aspiration holes
Number of holes
1
2
3
4
5
6
7
8
9
10
∅
of all aspiration
holes in mm
TP0F
1
PT
)
6,8
4,6
4,0
3,6
3,4
3,2
3,0
3,0
2,5
2,5
TP
1
PT
Opening diameter of the aspiration reduction film