Design
TITANUS
RACK·SENS
®
1U
4 –
22
Data: 03/09
TRS_A_04-en-e
4.4.3.5 Double-U-Pipe
system
1 Pipe system
TITANUS
RACK·SENS
®
1U
d
TI
TA
NU
S
R
A
C
K·S
EN
S
®
Fig. 4.16: Double-U-Pipe system, e.g. for equipment protection
Limit values
min. distance
TITANUS
P
®
P
– last T piece
0,2 m
max. distance
TITANUS
P
®
P
– last T piece
10 m
max. branch length
3,5 m
max. pipe length per pipe system
pipe
∅
25 mm
in addition to the pipe
∅
12 mm
15 m
8 x 3 m
max. number aspiration holes (n) per pipe system
8
maximum distance between the aspiration holes (d)
0,1 m
minimum distance between the aspiration holes (d)
4 m
Aspiration holes
Number of holes per
pipe system
4 8
∅
of all aspiration
holes in mm
TP3F
4
PT
)
4,4
3,0
TP
4
PT
Opening diameter of the aspiration reduction film