TITANUS
RACK·SENS
®
1U
Commissioning
TRS_A_07-en-e
Data: 03/09
7
– 19
7.3.1 Example of a commissioning log (2 pages)
Test
-------------------------------------------------------------------------
TITANUS RACK·SENS - [17.07.2007 15:33:19]
Serial No.: 1234567 Software No.: 0056.01.003 Parameter No.: 0056.001.001
Status
------
Fault -
Battery -
Mains -
Service/Blocked -
Released -
Fire alarm 1 -
Action alarm 1 -
Fire alarm 2 -
Action alarm 2 -
Detector module 1 Detector module 2
Serial No. 187448 187445
Software No. 0041.01.009 0041.01.009
Parameter No. 0041.100.001 0041.100.001
Smoke level 0,000 %/m 0,000 %/m
Detector state 2 % 0 %
Air flow 2 % (1,29 m/s)
Temperature 30,7 °C
Temperature Sensor: 1 2 3 4 5
29,1 °C 29,4 °C 29,0 °C 29,4 °C 29,5 °C
Settings A
----------
Alarm delay 10 s
Air flow range 30 %
Fault delay 1 min 40 s
Pre- warning time 10 s
Buzzer X
Fault latched -
Dynamic air flow -
Detector module 1 Detector module 2
Sensitivity (Fire alarm) 0,500 %/m 0,500 %/m
Action alarm threshold 60 % 60 %
LOGIC·SENS X X
Height above sea level 0 m
Air pressure 1013 hPa
Fan voltage 9,0 V
Settings B
----------
Programmable relay: 1 2 3 4 5
Fire alarm detector module 1 X - - - -
Action alarm detector module 1 - - X - -
Fire alarm detector module 2 - X - - -
Action alarm detector module 2 - - - X -
Temperature alarm 1 X - - - -
Temperature alarm 2 - X - - -
Temperature alarm 3 - - X - -
Temperature alarm 4 - - - X -
Temperature alarm 5 - - - - X
Logical OR X X X X X
Logical AND - - - - -
Temperature alarm: 1 2 3 4 5
60,0 °C 60,0 °C 60,0 °C 60,0 °C 60,0 °C