Troubleshooting Voltage Issues
GV Generators
wc_tx000772gb.fm
34
Continued from the previous page.
12.Disconnect the auto idle switch
(d)
and check it for continuity. It should have
continuity in the Auto position and no continuty in the OFF position.
Is the auto idle switch OK?
13.Start the engine.
14.Place the auto idle switch in the ON position.
This procedure continues on the next page.
Yes ____
No ____
Your reading
Reconnect the auto idle switch and
continue.
Replace the auto idle switch.
WARNING!
Electric shock hazard. High voltage exists at the components of the control
panel when the engine is running. Electric shock can cause severe injury or death.
f
Never touch any control panel component with your bare hands when the engine is run-
ning.