Cooling System
• High ambient temperature rated
• Factory filled with environmentally safe propylene glycol
• High temperature shutdown protection
Main Line Circuit Breaker
• UL 489 listed breaker is included as standard
• Conveniently mounted behind service door
Digital Remote Start/Stop Controller
• Automatic remote start (2-wire)
• Overspeed protection
• Overcrank protection
• Battery condition monitoring
• Underspeed protection
• On-off-auto selector switch
• Engine oil pressure protection
• Hour meter
Warranty
• 3 year / 1500 hour limited warranty (comprehensive)
• 5 year / 1500 hour extended limited warranty (engine/alternator)
Accessories
• Oil Pan Heater
• Maintenance Kit
P320100 / P320110
StAnDARD FeAtuReS
GM Vortec 3000 Industrial engine
• Ultra quiet and dependable automotive style inline 4 cylinder
operating at 1800 rpm
• Specially designed for use on LPG/natural gas
• Fuel efficient and durable design
• Electronic governing provides 0.5% frequency control
4-Pole Alternator
• 2/3 pitch winding for reduced harmonics (<5%)
• Tropicalized windings for corrosion resistance
Sound Attenuated Weather enclosure
• 16 gauge Galvaneel
™
(galvanized) steel or 12 gauge
aluminum with sound insulating material installed
• Powder coated almond color finish
• Modular design allows access from all sides
• Critical grade muffler integral to unit
Fuel System
• Operates on liquefied petroleum gas or natural gas
• Field convertible from natural gas to liquid propane
• Integrated governor-throttle body assembly
• Dual 12V DC positive lock-off valves for added safety
LIFe...unInteRRuPteD
™
1500 HOURS
ENTIRE SYSTEM
3
1500 HOURS
ENGINE/ALTERNATOR
5
SEE REVERSE SIDE FOR TECHNICAL SPECIFICATIONS
ALL SPECIFICATIONS SUBjECT TO CHANGE wITHOUT NOTICE
Models:
P320100
P320110
Output
Standby Rating
*
Full Load
Current
Motor
Starting
Alternator
Insulation
MLCB
Rating
Voltage
120/240
Hertz
60
Phase
1
kw
32LP
30NG
kVA
32
Amps
266.6/133.3
SkVA
(1)
50
Class
H
Amps
150
*NAMEPLATE RATING FOR CONTINUOUS STANDBy OPERATION FOR THE DURATION OF THE OUTAGE. DERATE 4% PER 1000 FEET
ABOVE 500 FEET. (1) RATED @ 30% VOLTAGE DIP.
101-3069-0308_P320100_Spec.indd 1