Troubleshooting Voltage Issues
wc_tx000772gb.fm
33
Continued from the previous page.
9. Start the engine.
10.Measure the DC voltage between the black/red (B/R) wire at the connector and
the white/black (W/B) wire of the auto idle unit.
Is at least 9.8VDC measured?
11.Shut down the engine.
This procedure continues on the next page.
WARNING!
Electric shock hazard. High voltage exists at the components of the control
panel when the engine is running. Electric shock can cause severe injury or death.
f
Never touch any control panel component with your bare hands when the engine is run-
ning.
Yes ____
No ____
Your reading
Continue.
The wiring has failed. Check the continuity of the
B/R wire and the continuity of the W/B wire.
VDC
B/R
W/B
1000
200
20
2
200m
F
V
VDC
A
V-
COM
wc_gr004361