I) Clock/Day Settings  

 

Clock 
set     Y/N 

 

This section of the menu permits the user to set the time and day. 

 

Time setting 

Day setting 

Time format setting 

Time 
set? Y/N 

No next 

 

Yes down 

 

Day 
set? Y/N 

No next 

 

Yes down 

 

12/24hrs 
set? Y/N 

No = exit 
Yes down 

 

Time 
0:00 

Use 

▲▼

 

To set value 

Day 
Monday 

Use 

▲▼

 

To set value 

12/24hrs 
12 hrs 

Use 

▲▼

 

To set value 

 

J) Schedule hold 

 

Schedule 
hold  Y/N 

This menu 
 

 

This menu will only appear on stand-alone thermostat, e.i. without a BACnet / Echelon module. 

 

This section of the menu permits the user to set a permanent schedule hold, which bypasses the internal 
thermostat scheduling.  

 

The permanent schedule hold function is typically used for non-scheduled events that extend for various periods 
of time. 

 

Enabling a permanent occupied or permanent unoccupied schedule hold will cancel any active override. 

 

The use of temporary setpoints during permanent hold is permitted. The duration of the temporary setpoint is as 
set per the TOccTime parameter. Ex. 3 hours 

 
Use 

▲▼

 to set value, Yes key to confirm 

 

Schedule 
resume 

 

 

Resume regular scheduling 

cancels the permanent hold and

 

re-enables the regular 

programming as set per internal scheduling or as per remote NSB via one of the DI’s 
configured as remote NSB.  

 

This action can also by accomplished by using the Resume menu. 

 

Any temporary setpoint that are active will be left active for the duration of the period as set 
per the TOccTime parameter. 

 

Schedule 
occ hold 

 

 

Hold permanent occupied 

forces the thermostat into a permanent occupied mode using the 

occupied setpoints. All timed scheduling functions are by-passed.  

 

The PERMANENT OCCUPIED

 

 status will appear in the automatic status scroll. To resume 

to regular scheduling, user must scroll to the Schedule Hold menu and select the Schedule 
resume option.. 

 

 

Schedule 
uno hold 

 

 

Hold permanent unoccupied 

forces the thermostat into a permanent unoccupied mode 

using the unoccupied setpoints. All timed scheduling functions are by-passed.  

 

The PERMANENT UNOCCUPIED status will appear in the automatic status scroll. To 
resume to regular scheduling, user must scroll to the Schedule Hold menu and select the 
Schedule resume option.. 
 

 

 

Содержание VT7607B5x28(X)

Страница 1: ...dy VT6x7 Series LonWorks Integration Guide VYKONStat PIR Application Guide VYKONStat PIR Cover Assembly Installation Guide VYKONStat Wireless Controller Application Guide Models Available Application...

Страница 2: ...2...

Страница 3: ...er alarm will be displayed on the thermostat LCD screen when the input is energized It can be tied to a differential pressure switch that monitor filters Rem NSB remote NSB timer clock input Will disa...

Страница 4: ...push on it until the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correc...

Страница 5: ...internal wiring Jumper J1 T1 24 Vac Cool Stage 2 Y2 Y1 Jumper J1 See note 1 previous page Fan RC G C Heat Stage 1 W1 RH W2 Auxiliary Output Field contact Com 24V Remote Outdoor Sensor Digital Input 0...

Страница 6: ...hermostat Remote humidity sensor accessories Model no Description VH2020W1028 Wall mounted humidity sensor VH2020D1028 Duct mounted humidity sensor VH2020W1028 remote wall mounted room humidity sensor...

Страница 7: ...e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o...

Страница 8: ...122 F indicates a shorted sensor Associated functions such as mode lockouts are automatically disabled A minimum range status 40 C 40 F is not displayed and indicates a opened sensor or a sensor not...

Страница 9: ...increase temperature setpoint and to adjust the desired values when programming and configuring the thermostat When left unattended for 45 seconds the display will resume automatic status display scr...

Страница 10: ...will be prompted with the present mode Heating or Cooling of the thermostat and its setpoint The Up arrow key will increment the setpoint by 0 5 degree F or C The Down arrow key will decrement the set...

Страница 11: ...ehumidification output is then activated There is NO active temperature lockout protection in this mode If the dehumidification process causes the room temperature to rise or fall the thermostat will...

Страница 12: ...00 00 AM Use To set value Unoccup 00 00 AM Use To set value Sets Event 2 Unoccupied time Will activate unoccupied setpoints Use to set value Yes key to confirm Typical examples of a 2 event office sc...

Страница 13: ...e Will activate unoccupied setpoints Use to set value Yes key to confirm Ex 1 Four event retail establishment schedule Event Period 1 Event 1 Period 1 Event 2 Period 2 Event 3 Period 2 Event 4 Setpoin...

Страница 14: ...3 hours Use to set value Yes key to confirm Schedule resume Resume regular scheduling cancels the permanent hold and re enables the regular programming as set per internal scheduling or as per remote...

Страница 15: ...orking address Default value 254 Range is 0 to 254 Conditional parameter to BACnet MS TP models VT76xxX5x28B Conditional parameter to Wireless models VT76xxX5x28W This parameter will only appear when...

Страница 16: ...ut the menu part related to scheduling is disabled and no longer accessible Open contact occupied setpoints Closed contacts unoccupied setpoints RemOVR Temporary override remote contact Disables all o...

Страница 17: ...32 C Maximum occupied unoccupied heating setpoint adjustment Heating setpoint range is 40 to 90 F 4 5 to 32 0 C Cool min Minimum cooling setpoint limit Default value 54 F 12 C Minimum occupied unoccup...

Страница 18: ...or On or Auto fan mode When selecting Off the fan terminal G when heating stages terminals W1 W2 are solicited will not be energized The fan in this case will be controlled by the equipment fan limit...

Страница 19: ...toggles from occupied to unoccupied after the last movement has been detected by the PIR Range is 0 5 to 24 0 hours in 0 5 hour increments 2 4event Number of events configuration Default value 2 even...

Страница 20: ...network value is transmitted to the thermostat See RH LT RE Sp From 20 F up to 55 F 6 5 C to 13 C HL Sp RH High limit setpoint Default value 85 RH High humidity limit in the supply Only valid if a 0 1...

Страница 21: ...et that can be added subtracted to actual displayed humidity by 15 0 RH This calibration applies to the internal humidity sensor if no remote humidity sensor is connected This calibration applies to t...

Страница 22: ...e 8 RE Sp was set to 20 therefore the humidity setpoint dropped from 45 to 20 If you don t want to use this feature set the RE Sp parameter to 90 RH High limit humidity sensor The VT76x7 series includ...

Страница 23: ...etpoint mode for the new setpoint to be kept and memory and used all the time 2 Go to the Set temperature menu 3 The last prompt is setpoint type Set it to Permanent setpoint Wrong mode selected Selec...

Страница 24: ...erify wiring Digital display shows missing digits or erratic segments Defective display Replace thermostat RH sensor is out of range Verify the remote RH sensor or the internal RH sensor System Mode i...

Страница 25: ...0 Vdc into 2K resistance min Humidification analog output accuracy 3 typical Wire gauge 18 gauge maximum 22 gauge recommended Dimensions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg...

Отзывы: