Installation  

  Remove security screw on the bottom of thermostat cover.  

  Open up by pulling on the bottom side of thermostat. 

  Remove Assembly and wiring terminals from sticker. 

(Fig. 3)

 

  Please note the FCC ID and IC label installed in the cover upon 

removal of cover for the wireless products. 

 
A) 

Location:

 

1- Should 

not be installed on an outside wall. 

2-  Must be installed away from any heat source. 
3-  Should not be installed near an air discharge grill. 
4-  Should not be affected by direct sun radiation. 
5-  Nothing must restrain vertical air circulation to the thermostat.

 

 
B) 

Installation:

 

1-  Swing open the thermostat PCB to the left by pressing the PCB 

locking tabs. 

(Fig. 4)

 

2-  Pull out cables 6” out of the wall.  
3-  Wall surface must be flat and clean.  
4-  Insert cable in the central hole of the base.

 

 

5-  Align the base and mark the location of the two mounting holes 

on the wall. Install proper side of base up. 

6-  Install anchors in the wall.

 

 

7-  Insert screws in mounting holes on each side of the base. 

(Fig. 4)

 

8-  Gently swing back the circuit board on the base and push on it 

until the tabs lock it. 

10- Strip each wire 1/4 inch. 
11- Insert each wire according to wiring diagram.  
13- Gently push back into hole excess wring 

(Fig. 5) 

14- Re-Install wiring terminals in correct location. 

(Fig. 5)

 

15- Reinstall the cover (top side first) and gently push back extra 

wire length into the hole in the wall.

 

16- Install security screw. 
 
 

  If replacing an old thermostat, label the wires before 

removal of the old thermostat. 

 

  Electronic controls are static sensitive devices.  

Discharge yourself properly before manipulation and 
installing the thermostat. 

 

  Short circuit or wrong wiring may permanently damage 

the thermostat or the equipment. 

 

  Anti-short cycling can be set to 0 minutes for equipment 

that posses their own anti cycling timer.  Do not use that 
value unless the equipment is equipped with such 
internal timer.  Failure to do so can damage the 
equipment. 

 

 

All VT7000 series thermostats are to be used only as 
operating controls.  Whenever a control failure could 
lead to personal injury and/or loss of property, it 
becomes the responsibility of the user to add safety 
devices and/or alarm system to protect against such 
catastrophic failures.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 
 
 
 

 

 
 
 
 
 
 
 
 

 

 

Re-install terminal blocks 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Thermostat assembly  

(VT7600B5x28 shown) 

 

 

 

 
 

 

Fig.3

Fig.5

Fig.4

Fig.6

Содержание VT7607B5x28(X)

Страница 1: ...dy VT6x7 Series LonWorks Integration Guide VYKONStat PIR Application Guide VYKONStat PIR Cover Assembly Installation Guide VYKONStat Wireless Controller Application Guide Models Available Application...

Страница 2: ...2...

Страница 3: ...er alarm will be displayed on the thermostat LCD screen when the input is energized It can be tied to a differential pressure switch that monitor filters Rem NSB remote NSB timer clock input Will disa...

Страница 4: ...push on it until the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correc...

Страница 5: ...internal wiring Jumper J1 T1 24 Vac Cool Stage 2 Y2 Y1 Jumper J1 See note 1 previous page Fan RC G C Heat Stage 1 W1 RH W2 Auxiliary Output Field contact Com 24V Remote Outdoor Sensor Digital Input 0...

Страница 6: ...hermostat Remote humidity sensor accessories Model no Description VH2020W1028 Wall mounted humidity sensor VH2020D1028 Duct mounted humidity sensor VH2020W1028 remote wall mounted room humidity sensor...

Страница 7: ...e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o...

Страница 8: ...122 F indicates a shorted sensor Associated functions such as mode lockouts are automatically disabled A minimum range status 40 C 40 F is not displayed and indicates a opened sensor or a sensor not...

Страница 9: ...increase temperature setpoint and to adjust the desired values when programming and configuring the thermostat When left unattended for 45 seconds the display will resume automatic status display scr...

Страница 10: ...will be prompted with the present mode Heating or Cooling of the thermostat and its setpoint The Up arrow key will increment the setpoint by 0 5 degree F or C The Down arrow key will decrement the set...

Страница 11: ...ehumidification output is then activated There is NO active temperature lockout protection in this mode If the dehumidification process causes the room temperature to rise or fall the thermostat will...

Страница 12: ...00 00 AM Use To set value Unoccup 00 00 AM Use To set value Sets Event 2 Unoccupied time Will activate unoccupied setpoints Use to set value Yes key to confirm Typical examples of a 2 event office sc...

Страница 13: ...e Will activate unoccupied setpoints Use to set value Yes key to confirm Ex 1 Four event retail establishment schedule Event Period 1 Event 1 Period 1 Event 2 Period 2 Event 3 Period 2 Event 4 Setpoin...

Страница 14: ...3 hours Use to set value Yes key to confirm Schedule resume Resume regular scheduling cancels the permanent hold and re enables the regular programming as set per internal scheduling or as per remote...

Страница 15: ...orking address Default value 254 Range is 0 to 254 Conditional parameter to BACnet MS TP models VT76xxX5x28B Conditional parameter to Wireless models VT76xxX5x28W This parameter will only appear when...

Страница 16: ...ut the menu part related to scheduling is disabled and no longer accessible Open contact occupied setpoints Closed contacts unoccupied setpoints RemOVR Temporary override remote contact Disables all o...

Страница 17: ...32 C Maximum occupied unoccupied heating setpoint adjustment Heating setpoint range is 40 to 90 F 4 5 to 32 0 C Cool min Minimum cooling setpoint limit Default value 54 F 12 C Minimum occupied unoccup...

Страница 18: ...or On or Auto fan mode When selecting Off the fan terminal G when heating stages terminals W1 W2 are solicited will not be energized The fan in this case will be controlled by the equipment fan limit...

Страница 19: ...toggles from occupied to unoccupied after the last movement has been detected by the PIR Range is 0 5 to 24 0 hours in 0 5 hour increments 2 4event Number of events configuration Default value 2 even...

Страница 20: ...network value is transmitted to the thermostat See RH LT RE Sp From 20 F up to 55 F 6 5 C to 13 C HL Sp RH High limit setpoint Default value 85 RH High humidity limit in the supply Only valid if a 0 1...

Страница 21: ...et that can be added subtracted to actual displayed humidity by 15 0 RH This calibration applies to the internal humidity sensor if no remote humidity sensor is connected This calibration applies to t...

Страница 22: ...e 8 RE Sp was set to 20 therefore the humidity setpoint dropped from 45 to 20 If you don t want to use this feature set the RE Sp parameter to 90 RH High limit humidity sensor The VT76x7 series includ...

Страница 23: ...etpoint mode for the new setpoint to be kept and memory and used all the time 2 Go to the Set temperature menu 3 The last prompt is setpoint type Set it to Permanent setpoint Wrong mode selected Selec...

Страница 24: ...erify wiring Digital display shows missing digits or erratic segments Defective display Replace thermostat RH sensor is out of range Verify the remote RH sensor or the internal RH sensor System Mode i...

Страница 25: ...0 Vdc into 2K resistance min Humidification analog output accuracy 3 typical Wire gauge 18 gauge maximum 22 gauge recommended Dimensions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg...

Отзывы: