domat UI09xx 

03/2017 Subject to technical changes. 

 

 

 

UI09x 

Communicative  room  unit  with  CO

2

 

sensor 

 

 

 

 

 

 

Summary 

The room unit with CO

2

 sensor contains temperature sensor, NDIR CO2 sensor for 

carbon  dioxide  concentration  measurement,  optional  humidity  sensor,  and 
control  knob  for  setpoint  control  and  other  settings.  The  binary  output  is 
controlled either on a remote basis, or as thermostat, hygrostat or CO

2

 controller. 

The units communicate over Modbus RTU / RS485 and they can be used as open 
system components with majority of building control system and controllers. 

 

Application 
 

 

Air handling units and air condition in rooms with variable load 

 

schools, cinemas, lecture halls etc. 

 

monitoring and recording of temperature, and CO

2

 concentration 

indoors 

 

Function 
 

The units acquire temperature, CO

2

 concentration, and optionally relative humidity in 

the  room,  temperature  correction  (controlled  by  the  knob)  and  required  operation 
status which is set by short push of the knob or in the menu. In the configurable menu 
following values can be set and displayed: 
 

 

temperature, actual temperature correction 

 

humidity (actual value only at room units containing the humidity sensor) 

 

time (only display at room units with RTC) 

 

basic setpoint - day 

 

basic setpoint - night 

 

outside temperature for heating enable 

 

DHW temperature 

 

heating curve type (1...4) 

 

operation mode  (Residential with Day, Night, Time  schedule, Off, or Hotel / 
Office with Comfort, Standby, Party, Off) 

 

fan stage (Auto, Off, St.1, St. 2, St. 3) 

 

A/C mode (Auto, Heating, Cooling, Off, Fan only) 

 

weekly scheduler: 7 days, up to 6 events per day 

Содержание UI090

Страница 1: ...onitoring and recording of temperature and CO2 concentration indoors Function The units acquire temperature CO2 concentration and optionally relative humidity in the room temperature correction controlled by the knob and required operation status which is set by short push of the knob or in the menu In the configurable menu following values can be set and displayed temperature actual temperature c...

Страница 2: ...dbus address and functionality is defined over the RS485 interface with service software ModComTool which is free for download at http domat int com en downloads software To interface the room unit to the computer use the USB 485 converter M080 RS232 RS485 converter M011 or any suitable RS485 converter Technical data Power supply 24 V AC 10 Consumption 600 mVA Temperature measuring range 20 70 C a...

Страница 3: ...ommon point 6 G0 power DI DO common point 7 G power 8 connector not installed 9 connector not installed DIP switches Back of the PCB BUS END if ON the bus is terminated if last device on the line USR not used reserved for future applications INIT sets the controller into default state and sets bus address to 1 baud rate to 9600 To init proceed as follows connect the device over RS485 to a PC with ...

Страница 4: ...the sensor may read values which differ from the real values by several hundreds ppm e g 200 ppm at night etc This error is automatically corrected with the first autocalibration Room unit as controller The binary output SSR if available may be controlled either from a PLC over the bus or configured as one of controllers thermostat hygrostat only at devices with rH sensor controller switching at a...

Страница 5: ... using Modbus RTU and thus they can be used in a number of control and SCADA systems The register description is available in a separate document Room units UI Communication description User manual for domat exe and detailed description of the room unit functions find in the document Room units configuration User manual Display Over Modbus it is possible to set reset the complete symbol set except...

Страница 6: ...ly with remote controlled input output if available For simple control applications control functions may be used see above Dimensions All dimensions in mm RoHS notice The device contains a non rechargeable battery which backups the real time clock and part of the memory After the device is not operable please return it to the manufacturer or dispose of it in compliance with local regulations ...

Страница 7: ...ges 7 Changes in versions 11 2015 Default values of ppm for 0 a 100 added 09 2016 Changed the format and reference to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours ...