domat UI090 Скачать руководство пользователя страница 2

 

03/2017 Subject to technical changes. 

domat UI09xx 

 

another 5 variables (air quality, fan speed etc.) 

 each has a profile where max. 

and min. values, step, number of decimals, and symbol set are defined. 

 
It is also possible to set / reset any of the LCD symbols on the display over Modbus. 
The turn / push knob has three basic functions: 
 

 

instant edit  (turning the knob) 

 settings of one predefined analogue value, 

usually room temperature correction 

 

quick edit (short push) 

 change of predefined state, e.g. Presence (Comfort / 

Standby / Off), Air condition (Auto / Heating / Cooling / Fan only / Off) etc. 

 

long push 

 jump to menu where values are listed by turning the knob, short 

push selects the value to be edited, and the value is changed by turning the 
knob followed by short push for confirmation.  

 
After  definable  inactivity  time,  the  display  goes  back  to  its  basic  state  with  rolling 
display of selected values (e.g. actual temperature and CO

2

). 

 
The unit Modbus address and functionality is defined over the RS485 interface with 
service  software 

ModComTool

  which  is  free  for  download  at 

http://domat-

int.com/en/downloads/software

. To interface the room unit to the computer use the 

USB/485  converter 

M080

,  RS232/RS485  converter 

M011

,  or  any  suitable  RS485 

converter. 
 

Technical data 
 

Power supply 

24 V AC +/- 10% 

Consumption 

600 mVA 

Temperature measuring range 

-

20 ÷ 70 °C, accuracy according to DIN IEC 751, Class B

 

Humidity (selected types only, see table 
below) 

10 ÷ 90 %rH (30

-70% +/- 3.5%, 10-90 +/- 4.5%) 

CO

2

 measuring range 

0 ... 5000 ppm  

CO

2

 measuring method 

NDIR (Non-dispersive Infra Red) 

CO

2

 measuring accuracy 

 30 ppm 

 5 % of measured value, software correction 

possible 

Reaction time of CO

2

 sensor (90 %) 

60 s 

Protection degree 

IP20 

Input 

1x for dry contact, 24 V AC, 5 mA 

Output 

1x  solid  state  relay,  zero  switching,  AC  load,  24  V  AC, 
maximum switched current 0,4 A 

Setpoint 

according to configuration, +/- 10 to +/- 1 K 

Communication 

RS485  -  Modbus  RTU,  slave,  selectable  speed  1200  ... 
115200 bps, N,8,1 

The interface is optically separated. 

Display 

LCD 60 x 60 mm, symbol set see above 

Terminals 

screw terminals for wires 0,14 

 1,5 mm

2

 

Содержание UI090

Страница 1: ...onitoring and recording of temperature and CO2 concentration indoors Function The units acquire temperature CO2 concentration and optionally relative humidity in the room temperature correction controlled by the knob and required operation status which is set by short push of the knob or in the menu In the configurable menu following values can be set and displayed temperature actual temperature c...

Страница 2: ...dbus address and functionality is defined over the RS485 interface with service software ModComTool which is free for download at http domat int com en downloads software To interface the room unit to the computer use the USB 485 converter M080 RS232 RS485 converter M011 or any suitable RS485 converter Technical data Power supply 24 V AC 10 Consumption 600 mVA Temperature measuring range 20 70 C a...

Страница 3: ...ommon point 6 G0 power DI DO common point 7 G power 8 connector not installed 9 connector not installed DIP switches Back of the PCB BUS END if ON the bus is terminated if last device on the line USR not used reserved for future applications INIT sets the controller into default state and sets bus address to 1 baud rate to 9600 To init proceed as follows connect the device over RS485 to a PC with ...

Страница 4: ...the sensor may read values which differ from the real values by several hundreds ppm e g 200 ppm at night etc This error is automatically corrected with the first autocalibration Room unit as controller The binary output SSR if available may be controlled either from a PLC over the bus or configured as one of controllers thermostat hygrostat only at devices with rH sensor controller switching at a...

Страница 5: ... using Modbus RTU and thus they can be used in a number of control and SCADA systems The register description is available in a separate document Room units UI Communication description User manual for domat exe and detailed description of the room unit functions find in the document Room units configuration User manual Display Over Modbus it is possible to set reset the complete symbol set except...

Страница 6: ...ly with remote controlled input output if available For simple control applications control functions may be used see above Dimensions All dimensions in mm RoHS notice The device contains a non rechargeable battery which backups the real time clock and part of the memory After the device is not operable please return it to the manufacturer or dispose of it in compliance with local regulations ...

Страница 7: ...ges 7 Changes in versions 11 2015 Default values of ppm for 0 a 100 added 09 2016 Changed the format and reference to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours ...