18

 

Heat cph 

Heating stages cycles per hour 
Default value = 

4 C.P.H. 

 

Will set the maximum number of heating stage cycles per 
hour under normal control operation.  It represents the 
maximum number of cycles that the equipment will turn ON 
and OFF in one hour. 
Note that a higher C.P.H will represent a higher accuracy of 
control at the expense of wearing mechanical components 
faster. 

3, 4, 5, 6,7 & 8 C.P.H. 

Cool cph 

Cooling stages cycles per hour 
Default value = 

4 C.P.H. 

 

Will set the maximum number of cooling stage cycles per 
hour under normal control operation. It represents the 
maximum number of cycles that the equipment will turned on 
and off in one hour. 
Note that a higher C.P.H will represent a higher accuracy of 
control at the expense of wearing mechanical components 
faster. 

3 or 4 C.P.H.

 

Deadband 

Minimum deadband 
Default value = 

2.0 °F ( 1.1 °C )

 

Minimum deadband value between the heating and cooling 
setpoints. If modified, it will be applied only when any of the 
setpoints are modified. 

2, 3 or 4 °F ( 1.0 to 2.0 °C ) 

Fan cont 

Fan control 
Default value = 

On 

 

 

 

Fan control in heating mode. 
When selecting 

On

; the thermostat in all cases will always 

control the fan (terminal G).  
Valid for On or Auto fan mode 
When selecting 

Off

; the fan ( terminal G ), when heating 

stages ( terminals W1 & W2 ) are solicited, will not be 
energized. The fan in this case will be controlled by the 
equipment fan limit control. 
Valid only for Auto fan mode. On fan mode will leave the fan 
always on. 

On or Off 

Fan del 

Fan delay 
Default value = 

Off

 

Fan delay extends fan operation by 60 seconds after the call 
for heating or cooling ends. 
Valid only for Auto fan mode. “On” fan mode will leave the fan 
always on. 

Off or On 

TOccTime 

Temporary occupancy time 
Default value = 

3 hours

 

Temporary occupancy time with occupied mode setpoints 
when override function is enabled 
When the thermostat is in unoccupied mode, function is 
enabled with either the menu or DI1 or DI2 configured as 
remote override input. 

0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 & 12 hours 

Cal RS 

Room air temperature sensor 
calibration 
Default value = 

0.0 °F or °C

 

Offset that can be added/subtracted to actual displayed room 
temperature  

± 5.0 °F ( ± 2.5 °C ) 

Cal OS 

Outside air temperature sensor 
calibration 
Default value = 

0.0 °F or °C

 

Offset that can be added/subtracted to actual displayed 
outside air temperature  

± 5.0 °F ( ± 2.5 °C )

 

H stage 

Number of heating stages.  Applicable 
to 2 stage models only 
Default value = 

2 stages

 

Will revert the operation of 2 stages thermostat to single 
stage operation only when the second heating step is not 
needed. 

1 or 2 stages 

Содержание VT7607B5x28(X)

Страница 1: ...dy VT6x7 Series LonWorks Integration Guide VYKONStat PIR Application Guide VYKONStat PIR Cover Assembly Installation Guide VYKONStat Wireless Controller Application Guide Models Available Application...

Страница 2: ...2...

Страница 3: ...er alarm will be displayed on the thermostat LCD screen when the input is energized It can be tied to a differential pressure switch that monitor filters Rem NSB remote NSB timer clock input Will disa...

Страница 4: ...push on it until the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correc...

Страница 5: ...internal wiring Jumper J1 T1 24 Vac Cool Stage 2 Y2 Y1 Jumper J1 See note 1 previous page Fan RC G C Heat Stage 1 W1 RH W2 Auxiliary Output Field contact Com 24V Remote Outdoor Sensor Digital Input 0...

Страница 6: ...hermostat Remote humidity sensor accessories Model no Description VH2020W1028 Wall mounted humidity sensor VH2020D1028 Duct mounted humidity sensor VH2020W1028 remote wall mounted room humidity sensor...

Страница 7: ...e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o...

Страница 8: ...122 F indicates a shorted sensor Associated functions such as mode lockouts are automatically disabled A minimum range status 40 C 40 F is not displayed and indicates a opened sensor or a sensor not...

Страница 9: ...increase temperature setpoint and to adjust the desired values when programming and configuring the thermostat When left unattended for 45 seconds the display will resume automatic status display scr...

Страница 10: ...will be prompted with the present mode Heating or Cooling of the thermostat and its setpoint The Up arrow key will increment the setpoint by 0 5 degree F or C The Down arrow key will decrement the set...

Страница 11: ...ehumidification output is then activated There is NO active temperature lockout protection in this mode If the dehumidification process causes the room temperature to rise or fall the thermostat will...

Страница 12: ...00 00 AM Use To set value Unoccup 00 00 AM Use To set value Sets Event 2 Unoccupied time Will activate unoccupied setpoints Use to set value Yes key to confirm Typical examples of a 2 event office sc...

Страница 13: ...e Will activate unoccupied setpoints Use to set value Yes key to confirm Ex 1 Four event retail establishment schedule Event Period 1 Event 1 Period 1 Event 2 Period 2 Event 3 Period 2 Event 4 Setpoin...

Страница 14: ...3 hours Use to set value Yes key to confirm Schedule resume Resume regular scheduling cancels the permanent hold and re enables the regular programming as set per internal scheduling or as per remote...

Страница 15: ...orking address Default value 254 Range is 0 to 254 Conditional parameter to BACnet MS TP models VT76xxX5x28B Conditional parameter to Wireless models VT76xxX5x28W This parameter will only appear when...

Страница 16: ...ut the menu part related to scheduling is disabled and no longer accessible Open contact occupied setpoints Closed contacts unoccupied setpoints RemOVR Temporary override remote contact Disables all o...

Страница 17: ...32 C Maximum occupied unoccupied heating setpoint adjustment Heating setpoint range is 40 to 90 F 4 5 to 32 0 C Cool min Minimum cooling setpoint limit Default value 54 F 12 C Minimum occupied unoccup...

Страница 18: ...or On or Auto fan mode When selecting Off the fan terminal G when heating stages terminals W1 W2 are solicited will not be energized The fan in this case will be controlled by the equipment fan limit...

Страница 19: ...toggles from occupied to unoccupied after the last movement has been detected by the PIR Range is 0 5 to 24 0 hours in 0 5 hour increments 2 4event Number of events configuration Default value 2 even...

Страница 20: ...network value is transmitted to the thermostat See RH LT RE Sp From 20 F up to 55 F 6 5 C to 13 C HL Sp RH High limit setpoint Default value 85 RH High humidity limit in the supply Only valid if a 0 1...

Страница 21: ...et that can be added subtracted to actual displayed humidity by 15 0 RH This calibration applies to the internal humidity sensor if no remote humidity sensor is connected This calibration applies to t...

Страница 22: ...e 8 RE Sp was set to 20 therefore the humidity setpoint dropped from 45 to 20 If you don t want to use this feature set the RE Sp parameter to 90 RH High limit humidity sensor The VT76x7 series includ...

Страница 23: ...etpoint mode for the new setpoint to be kept and memory and used all the time 2 Go to the Set temperature menu 3 The last prompt is setpoint type Set it to Permanent setpoint Wrong mode selected Selec...

Страница 24: ...erify wiring Digital display shows missing digits or erratic segments Defective display Replace thermostat RH sensor is out of range Verify the remote RH sensor or the internal RH sensor System Mode i...

Страница 25: ...0 Vdc into 2K resistance min Humidification analog output accuracy 3 typical Wire gauge 18 gauge maximum 22 gauge recommended Dimensions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg...

Отзывы: