background image

 

9

2. User programming instructions menu 

 

The VT7600 series of thermostat feature an intuitive, menu-driven, backlit LCD display that walks users through the 
programming steps, making the programming process extremely simple.  This menu is typically accessed by the user to set the 
parameters such as temperature and time events, system mode, fan mode, etc. 

 

It is possible to bring up the user menu at any time by depressing the MENU key. The status display automatically resumes 
after exiting the user-programming menu.

 

 

If the user pauses at any given time during programming, 

Auto Help

 text is displayed to help and guide the user through the 

usage and programming of the thermostat. 

 
 

Ex.: 

 

Press yes key to change cooling temperature setpoint 
Use the up or down arrow to adjust cooling setpoint

 

 

Each of the sections in the menu are accessed and programmed using 5 keys on the thermostat cover. 
The priority for the alarms is as follows: 

 
 

 
 
 

 

The YES key is used to confirm a selection, to move onto the next menu item and to manually scroll through the 
displayed information. 

 
 
 

 

The NO key is used when you do not desire a parameter change, and to advance to the next menu item.  Can 
also be used to toggle between heating and cooling setpoints. 

 
 
 

  The MENU key is used to access the Main User Menu or exit the menu. 

 
 
 

 

The down arrow key is used to decrease temperature setpoint and to adjust the desired values when 
programming and configuring the thermostat.

 

 
 
 

 

The up arrow key is used to increase temperature setpoint and to adjust the desired values when programming 
and configuring the thermostat. 

 

When left unattended for 45 seconds, the display will resume automatic status display scrolling. 
To turn on the backlit, press any key on the front panel. The backlit display will turn off when the thermostat is left unattended 
for 45 seconds 

 
Sequence of user menu: 

 

Override 

Resume 

 

Temperature 

setpoints 

 Humidity 

setpoints 

 

System mode 

setting 

Fan mode 

setting 

Schedules 

setting 

Clock 

setting 

 Schedule 

hold 

Override 
schd Y/N 

 

Temperat 
set     Y/N 

 

Humidity 
set    Y/N 

 

Sys mode 
set   Y/N 

 

Fan mode 
set  Y/N 

Schedule 
set   Y/N 

Clock 
set Y/N 

 

Schedule 
hold  Y/N 

Appears only in 
unoccupied mode 

   

   

  

 

 

 

  Appears only on 

stand-alone models 

Cancel  
ovrd Y/N 

 

 

   

  

 

 

 

  

Appears only in 
override mode 

   

   

  

 

 

 

  

 
 

There is a default profile set in the thermostat from the factory. 
This enables the thermostat to operate as a non-programmable unit in day mode operation at start up. 

 

Programmed default temperature and humidity setpoints: 

 

Programmed default modes: 

Occupied cooling setpoint = 24 °C ( 75 °F ) 

 

System mode = Auto 

Occupied heating setpoint = 22 °C ( 72 °F ) 

Unoccupied cooling setpoint = 28 °C ( 82 °F ) 

 

Fan mode = Smart (for models with a communication module or 

programmable stand-alone models) 

Fan mode = Auto (for non-programmable stand-alone models) 

Unoccupied heating setpoint = 18 °C ( 65 °F ) 

 

Programmed default schedules: 

Dehumidification setpoint = 70% RH 

 

Monday through Sunday 

Humidification setpoint = 50% RH 

 

Occupied time is: 12 00 AM 

Fahrenheit scale  

 

Unoccupied time is: 11:59 PM 

Setpoint type = permanent 

 

Unoccupied time is: 11:59 PM 

 

 
There will be a 1 minute unoccupied period every night at 11:59 PM with this default configuration. 

Содержание VT7607B5x28(X)

Страница 1: ...dy VT6x7 Series LonWorks Integration Guide VYKONStat PIR Application Guide VYKONStat PIR Cover Assembly Installation Guide VYKONStat Wireless Controller Application Guide Models Available Application...

Страница 2: ...2...

Страница 3: ...er alarm will be displayed on the thermostat LCD screen when the input is energized It can be tied to a differential pressure switch that monitor filters Rem NSB remote NSB timer clock input Will disa...

Страница 4: ...push on it until the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correc...

Страница 5: ...internal wiring Jumper J1 T1 24 Vac Cool Stage 2 Y2 Y1 Jumper J1 See note 1 previous page Fan RC G C Heat Stage 1 W1 RH W2 Auxiliary Output Field contact Com 24V Remote Outdoor Sensor Digital Input 0...

Страница 6: ...hermostat Remote humidity sensor accessories Model no Description VH2020W1028 Wall mounted humidity sensor VH2020D1028 Duct mounted humidity sensor VH2020W1028 remote wall mounted room humidity sensor...

Страница 7: ...e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o...

Страница 8: ...122 F indicates a shorted sensor Associated functions such as mode lockouts are automatically disabled A minimum range status 40 C 40 F is not displayed and indicates a opened sensor or a sensor not...

Страница 9: ...increase temperature setpoint and to adjust the desired values when programming and configuring the thermostat When left unattended for 45 seconds the display will resume automatic status display scr...

Страница 10: ...will be prompted with the present mode Heating or Cooling of the thermostat and its setpoint The Up arrow key will increment the setpoint by 0 5 degree F or C The Down arrow key will decrement the set...

Страница 11: ...ehumidification output is then activated There is NO active temperature lockout protection in this mode If the dehumidification process causes the room temperature to rise or fall the thermostat will...

Страница 12: ...00 00 AM Use To set value Unoccup 00 00 AM Use To set value Sets Event 2 Unoccupied time Will activate unoccupied setpoints Use to set value Yes key to confirm Typical examples of a 2 event office sc...

Страница 13: ...e Will activate unoccupied setpoints Use to set value Yes key to confirm Ex 1 Four event retail establishment schedule Event Period 1 Event 1 Period 1 Event 2 Period 2 Event 3 Period 2 Event 4 Setpoin...

Страница 14: ...3 hours Use to set value Yes key to confirm Schedule resume Resume regular scheduling cancels the permanent hold and re enables the regular programming as set per internal scheduling or as per remote...

Страница 15: ...orking address Default value 254 Range is 0 to 254 Conditional parameter to BACnet MS TP models VT76xxX5x28B Conditional parameter to Wireless models VT76xxX5x28W This parameter will only appear when...

Страница 16: ...ut the menu part related to scheduling is disabled and no longer accessible Open contact occupied setpoints Closed contacts unoccupied setpoints RemOVR Temporary override remote contact Disables all o...

Страница 17: ...32 C Maximum occupied unoccupied heating setpoint adjustment Heating setpoint range is 40 to 90 F 4 5 to 32 0 C Cool min Minimum cooling setpoint limit Default value 54 F 12 C Minimum occupied unoccup...

Страница 18: ...or On or Auto fan mode When selecting Off the fan terminal G when heating stages terminals W1 W2 are solicited will not be energized The fan in this case will be controlled by the equipment fan limit...

Страница 19: ...toggles from occupied to unoccupied after the last movement has been detected by the PIR Range is 0 5 to 24 0 hours in 0 5 hour increments 2 4event Number of events configuration Default value 2 even...

Страница 20: ...network value is transmitted to the thermostat See RH LT RE Sp From 20 F up to 55 F 6 5 C to 13 C HL Sp RH High limit setpoint Default value 85 RH High humidity limit in the supply Only valid if a 0 1...

Страница 21: ...et that can be added subtracted to actual displayed humidity by 15 0 RH This calibration applies to the internal humidity sensor if no remote humidity sensor is connected This calibration applies to t...

Страница 22: ...e 8 RE Sp was set to 20 therefore the humidity setpoint dropped from 45 to 20 If you don t want to use this feature set the RE Sp parameter to 90 RH High limit humidity sensor The VT76x7 series includ...

Страница 23: ...etpoint mode for the new setpoint to be kept and memory and used all the time 2 Go to the Set temperature menu 3 The last prompt is setpoint type Set it to Permanent setpoint Wrong mode selected Selec...

Страница 24: ...erify wiring Digital display shows missing digits or erratic segments Defective display Replace thermostat RH sensor is out of range Verify the remote RH sensor or the internal RH sensor System Mode i...

Страница 25: ...0 Vdc into 2K resistance min Humidification analog output accuracy 3 typical Wire gauge 18 gauge maximum 22 gauge recommended Dimensions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg...

Отзывы: