15

 

 

Installer configuration parameter menu  

 

-

 

Configuration can be done through the network or locally at the thermostat. 

-

 

To enter configuration, press and hold the middle button “Menu

 for 8 seconds 

-

 

If a password lockout is active, “

Password

” is prompted. Enter password value using the “

up

” and “

down

” 

arrows and press “

Yes

” to gain access to all configuration properties of the thermostat. A wrong password 

entered will prevent local access to the configuration menu. 

-

 

Once in the configuration menu, press the “

No

” button repetitively to scroll between all the available 

parameters.  

-

 

When the desired parameter is displayed, press “

Yes

” to adjust it to the desired value using “

up

” and 

down

” arrows. Once set, press “

Yes

” to scroll to the next parameter. 

Configuration 

parameters 

Significance 

Default value 

Adjustments 

Pswrd 

Configuration parameters menu access 
password 

 

Default value = 

0 ( no password 

prompted )

 

This parameter sets a protective access password to 
prevent unauthorized access to the configuration menu 
parameters. A default value of “0” will not prompt a 
password or lock the access to the configuration menu. 

 

Range is:

 

0 to 1000 

Com addr 

Thermostat networking address 

 

Default value = 

254

  

 

Range is:

 0 to 254

 

Conditional parameter to BACnet MS-TP models 
(VT76xxX5x28B) 

Conditional parameter to Wireless models 
(VT76xxX5x28W) 

This parameter will only appear when a BACnet or 
wireless network adapter is present. If the thermostat is 
installed as a stand-alone unit or with an Echelon 
adapter, this parameter will not be used or displayed 

-

 

For BACnet MS-TP models valid range to use is 
from 1 to 127. Default value of 254 disables BACnet 
communication for the thermostat. 

-

 

For wireless models valid range is 0 to 254 with a 
maximum of 30 thermostat per VWG 

PAN ID 

Personal Area Network Identification 

 

Default value = 

 

Range is:

 0 to 500 

 

Conditional parameter to Wireless models 
(VT76xxX5x28W) 

This parameter will only appear when a wireless network 
adapter is present. If the thermostat is installed as a stand-
alone unit or with a BACnet or Echelon adapter, this parameter 
will not be used or displayed 
 
This parameter (Personal Area Network Identification) is used 
to link specific thermostats to a single specific Vykon JACE 
with wireless network adapter.  For every thermostat reporting 
to a JACE (maximum of 30 wireless thermostats), be sure you 
set the 

SAME

 PAN ID value both at the JACE and the 

thermostat(s).  
 

The default value of 0 is 

NOT

 a valid PAN ID. The valid range 

of available PAN ID is from 1 to 500

 

 

Содержание VT7607B5x28(X)

Страница 1: ...dy VT6x7 Series LonWorks Integration Guide VYKONStat PIR Application Guide VYKONStat PIR Cover Assembly Installation Guide VYKONStat Wireless Controller Application Guide Models Available Application...

Страница 2: ...2...

Страница 3: ...er alarm will be displayed on the thermostat LCD screen when the input is energized It can be tied to a differential pressure switch that monitor filters Rem NSB remote NSB timer clock input Will disa...

Страница 4: ...push on it until the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correc...

Страница 5: ...internal wiring Jumper J1 T1 24 Vac Cool Stage 2 Y2 Y1 Jumper J1 See note 1 previous page Fan RC G C Heat Stage 1 W1 RH W2 Auxiliary Output Field contact Com 24V Remote Outdoor Sensor Digital Input 0...

Страница 6: ...hermostat Remote humidity sensor accessories Model no Description VH2020W1028 Wall mounted humidity sensor VH2020D1028 Duct mounted humidity sensor VH2020W1028 remote wall mounted room humidity sensor...

Страница 7: ...e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o...

Страница 8: ...122 F indicates a shorted sensor Associated functions such as mode lockouts are automatically disabled A minimum range status 40 C 40 F is not displayed and indicates a opened sensor or a sensor not...

Страница 9: ...increase temperature setpoint and to adjust the desired values when programming and configuring the thermostat When left unattended for 45 seconds the display will resume automatic status display scr...

Страница 10: ...will be prompted with the present mode Heating or Cooling of the thermostat and its setpoint The Up arrow key will increment the setpoint by 0 5 degree F or C The Down arrow key will decrement the set...

Страница 11: ...ehumidification output is then activated There is NO active temperature lockout protection in this mode If the dehumidification process causes the room temperature to rise or fall the thermostat will...

Страница 12: ...00 00 AM Use To set value Unoccup 00 00 AM Use To set value Sets Event 2 Unoccupied time Will activate unoccupied setpoints Use to set value Yes key to confirm Typical examples of a 2 event office sc...

Страница 13: ...e Will activate unoccupied setpoints Use to set value Yes key to confirm Ex 1 Four event retail establishment schedule Event Period 1 Event 1 Period 1 Event 2 Period 2 Event 3 Period 2 Event 4 Setpoin...

Страница 14: ...3 hours Use to set value Yes key to confirm Schedule resume Resume regular scheduling cancels the permanent hold and re enables the regular programming as set per internal scheduling or as per remote...

Страница 15: ...orking address Default value 254 Range is 0 to 254 Conditional parameter to BACnet MS TP models VT76xxX5x28B Conditional parameter to Wireless models VT76xxX5x28W This parameter will only appear when...

Страница 16: ...ut the menu part related to scheduling is disabled and no longer accessible Open contact occupied setpoints Closed contacts unoccupied setpoints RemOVR Temporary override remote contact Disables all o...

Страница 17: ...32 C Maximum occupied unoccupied heating setpoint adjustment Heating setpoint range is 40 to 90 F 4 5 to 32 0 C Cool min Minimum cooling setpoint limit Default value 54 F 12 C Minimum occupied unoccup...

Страница 18: ...or On or Auto fan mode When selecting Off the fan terminal G when heating stages terminals W1 W2 are solicited will not be energized The fan in this case will be controlled by the equipment fan limit...

Страница 19: ...toggles from occupied to unoccupied after the last movement has been detected by the PIR Range is 0 5 to 24 0 hours in 0 5 hour increments 2 4event Number of events configuration Default value 2 even...

Страница 20: ...network value is transmitted to the thermostat See RH LT RE Sp From 20 F up to 55 F 6 5 C to 13 C HL Sp RH High limit setpoint Default value 85 RH High humidity limit in the supply Only valid if a 0 1...

Страница 21: ...et that can be added subtracted to actual displayed humidity by 15 0 RH This calibration applies to the internal humidity sensor if no remote humidity sensor is connected This calibration applies to t...

Страница 22: ...e 8 RE Sp was set to 20 therefore the humidity setpoint dropped from 45 to 20 If you don t want to use this feature set the RE Sp parameter to 90 RH High limit humidity sensor The VT76x7 series includ...

Страница 23: ...etpoint mode for the new setpoint to be kept and memory and used all the time 2 Go to the Set temperature menu 3 The last prompt is setpoint type Set it to Permanent setpoint Wrong mode selected Selec...

Страница 24: ...erify wiring Digital display shows missing digits or erratic segments Defective display Replace thermostat RH sensor is out of range Verify the remote RH sensor or the internal RH sensor System Mode i...

Страница 25: ...0 Vdc into 2K resistance min Humidification analog output accuracy 3 typical Wire gauge 18 gauge maximum 22 gauge recommended Dimensions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg...

Отзывы: