Important Notice  

 

 

All VT7600 series controls are 
for use as operating controls 
only and are not safety 
devices. These 

 

instruments have undergone rigorous 

tests and verifications prior to shipment to 
ensure proper and reliable operation in 
the field.  Whenever a control failure could 
lead to personal injury and/or loss of 
property, it becomes the responsibility of 
the user / installer / electrical system 
designer to incorporate safety devices ( 
such as relays, flow switch, thermal 
protections, etc…) and/or alarm system to 
protect the entire system against such 
catastrophic failures.  Tampering of the 
devices or miss application of the device 
will void warranty. 

 

Specifications  

 

 

Thermostat power requirements:  19-30 Vac  50 or 60 Hz; 2 VA ( RC & C ) Class 2 

  RC to RH jumper 2.0 Amps 48 VA maximum  

Operating conditions:  0 °C to 50 °C ( 32 °F to 122 °F ) 

  0% to 95% R.H. non-condensing 

Storage conditions:  -30 °C to 50 °C ( -22 °F to 122 °F ) 

  0% to 95% R.H. non-condensing 

Temperature sensor:  Local 10 K NTC thermistor 

Resolution:  Temperature: ± 0.1 °C (± 0.2 °F) 

Humidity: ± 0.1% 

Control accuracy:  Temp: ± 0.5 ° C  ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typ. calibrated 

Humidity: ± 5% RH from 20 to 0% RH at 50 to 90°F (10 to 32°C) 

Humidification setpoint range:  10% RH to 90% RH 

Dehumidification setpoint range:  15% RH to 95% RH 

Occupied and unoccupied setpoint range cooling:  12.0 to 37.5 °C ( 54 to 100 °F ) 

Occupied and unoccupied setpoint range heating:  4.5 °C to 32 °C ( 40 °F to 90 °F ) 

Room and outdoor air temperature range  -40 °C to 50 °C ( -40 °F to 122 °F ) 

Proportional band for room temperature control:  Factory set, heating and cooling at: 1.1°C ( 2.0°F ) 

Digital input:  Relay dry contact only across C terminal to DI1 

Analog high limit and remote humidity inputs  0 to 10 Vdc into 10K

Ω

 input load 

Contact output rating:  Each relay output: ( Y1, Y2, G, W1, W2 & AU ) 

30 Vac, 1 Amp. maximum  
30 Vac, 3 Amp. in-rush 

Humidification analog output rating:  0 to 10 Vdc into 2K

Ω

 resistance min. 

Humidification analog output accuracy:  ± 3% typical 

Wire gauge  18 gauge maximum, 22 gauge recommended 

Dimensions: 4.94” 

x 3.38” x 1.13” 

Approximate shipping weight:  0.75 lb ( 0.34 kg ) 

Agency Approvals all models: 

UL:

 UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with 

CCN XAPX (US) and XAPX7 (Canada) 

 

Industry Canada: 

ICES-003 (Canada) 

Agency Approvals all models 

FCC: 

Compliant to CFR 47, Part 15, Subpart B, Class A (US) 

 

CE: 

EMC Directive 89/336/EEC (Europe Union) 

 

C-Tick: 

AS/NZS CISPR 22 Compliant (Australia / New Zealand) 

Supplier Code Number N10696 

Agency Approvals Wireless models 

FCC: 

Compliant to: Part 15, Subpart C 

THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO 
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY 
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.

 

Drawing & dimensions  

 

 

 

 

 

 

 

Vykon and WEEE 

 

The Waste Electrical and Electronic Equipment (WEEE) mark applies only to countries within the European Union (EU) and Norway. 
Electric/Electronic devices are labeled in accordance with European Directive 2002/96/EC concerning waste electrical and electronic 
equipment (WEEE). The Directive determines the framework for the return and recycling of used Electric/Electronic devices at the end of 
life within and throughout the European Union (EU). This label is applied to various products to indicate the product is not to be thrown 
away, but rather be reclaimed upon the end of the products useful life per this directive. 
Users of electric and electronic equipment with the WEEE marking per annex IV of the WEEE Directive must not dispose of end of life 
Electric/Electronic waste as unsorted municipal waste, but rather use the collection framework available to them for the return, recycle and 
recovery of WEEE and minimize the environmental impact of Electric/Electronic waste due to the presence of hazardous substance. 
FoFig.13 – Thermostat dimensions 

Содержание VT7607B5x28(X)

Страница 1: ...dy VT6x7 Series LonWorks Integration Guide VYKONStat PIR Application Guide VYKONStat PIR Cover Assembly Installation Guide VYKONStat Wireless Controller Application Guide Models Available Application...

Страница 2: ...2...

Страница 3: ...er alarm will be displayed on the thermostat LCD screen when the input is energized It can be tied to a differential pressure switch that monitor filters Rem NSB remote NSB timer clock input Will disa...

Страница 4: ...push on it until the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correc...

Страница 5: ...internal wiring Jumper J1 T1 24 Vac Cool Stage 2 Y2 Y1 Jumper J1 See note 1 previous page Fan RC G C Heat Stage 1 W1 RH W2 Auxiliary Output Field contact Com 24V Remote Outdoor Sensor Digital Input 0...

Страница 6: ...hermostat Remote humidity sensor accessories Model no Description VH2020W1028 Wall mounted humidity sensor VH2020D1028 Duct mounted humidity sensor VH2020W1028 remote wall mounted room humidity sensor...

Страница 7: ...e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o...

Страница 8: ...122 F indicates a shorted sensor Associated functions such as mode lockouts are automatically disabled A minimum range status 40 C 40 F is not displayed and indicates a opened sensor or a sensor not...

Страница 9: ...increase temperature setpoint and to adjust the desired values when programming and configuring the thermostat When left unattended for 45 seconds the display will resume automatic status display scr...

Страница 10: ...will be prompted with the present mode Heating or Cooling of the thermostat and its setpoint The Up arrow key will increment the setpoint by 0 5 degree F or C The Down arrow key will decrement the set...

Страница 11: ...ehumidification output is then activated There is NO active temperature lockout protection in this mode If the dehumidification process causes the room temperature to rise or fall the thermostat will...

Страница 12: ...00 00 AM Use To set value Unoccup 00 00 AM Use To set value Sets Event 2 Unoccupied time Will activate unoccupied setpoints Use to set value Yes key to confirm Typical examples of a 2 event office sc...

Страница 13: ...e Will activate unoccupied setpoints Use to set value Yes key to confirm Ex 1 Four event retail establishment schedule Event Period 1 Event 1 Period 1 Event 2 Period 2 Event 3 Period 2 Event 4 Setpoin...

Страница 14: ...3 hours Use to set value Yes key to confirm Schedule resume Resume regular scheduling cancels the permanent hold and re enables the regular programming as set per internal scheduling or as per remote...

Страница 15: ...orking address Default value 254 Range is 0 to 254 Conditional parameter to BACnet MS TP models VT76xxX5x28B Conditional parameter to Wireless models VT76xxX5x28W This parameter will only appear when...

Страница 16: ...ut the menu part related to scheduling is disabled and no longer accessible Open contact occupied setpoints Closed contacts unoccupied setpoints RemOVR Temporary override remote contact Disables all o...

Страница 17: ...32 C Maximum occupied unoccupied heating setpoint adjustment Heating setpoint range is 40 to 90 F 4 5 to 32 0 C Cool min Minimum cooling setpoint limit Default value 54 F 12 C Minimum occupied unoccup...

Страница 18: ...or On or Auto fan mode When selecting Off the fan terminal G when heating stages terminals W1 W2 are solicited will not be energized The fan in this case will be controlled by the equipment fan limit...

Страница 19: ...toggles from occupied to unoccupied after the last movement has been detected by the PIR Range is 0 5 to 24 0 hours in 0 5 hour increments 2 4event Number of events configuration Default value 2 even...

Страница 20: ...network value is transmitted to the thermostat See RH LT RE Sp From 20 F up to 55 F 6 5 C to 13 C HL Sp RH High limit setpoint Default value 85 RH High humidity limit in the supply Only valid if a 0 1...

Страница 21: ...et that can be added subtracted to actual displayed humidity by 15 0 RH This calibration applies to the internal humidity sensor if no remote humidity sensor is connected This calibration applies to t...

Страница 22: ...e 8 RE Sp was set to 20 therefore the humidity setpoint dropped from 45 to 20 If you don t want to use this feature set the RE Sp parameter to 90 RH High limit humidity sensor The VT76x7 series includ...

Страница 23: ...etpoint mode for the new setpoint to be kept and memory and used all the time 2 Go to the Set temperature menu 3 The last prompt is setpoint type Set it to Permanent setpoint Wrong mode selected Selec...

Страница 24: ...erify wiring Digital display shows missing digits or erratic segments Defective display Replace thermostat RH sensor is out of range Verify the remote RH sensor or the internal RH sensor System Mode i...

Страница 25: ...0 Vdc into 2K resistance min Humidification analog output accuracy 3 typical Wire gauge 18 gauge maximum 22 gauge recommended Dimensions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg...

Отзывы: