 A) Override an unoccupied period 

 

Override 
schd Y/N 

 

This menu will appear only when the thermostat is in unoccupied mode. The unoccupied mode is enabled either by the internal 
timer scheduling or by a remote NSB contact via DI. 
If DI is configured to operate as a remote temporary override contact, this menu will be disabled. 

 

Answering yes to this prompt will cause the thermostat to go into occupied mode for an amount of time equal to the parameter 
“TOccTime” (1 to 12 hours). 

 

B) Resume regular scheduling 

 

Cancel  
ovrd Y/N 

 

This menu does not appear in regular operation. It will appear only when the thermostat is in Unoccupied override mode. 
Answering “Yes” to this question will cause the thermostat to resume the regular programmed setpoints & scheduling.  

 

C) Temperature setpoints 

 

Permanent setpoint changes 

 

 

Temperat 
set     Y/N 

 

This menu permits the adjustment of all permanent temperature setpoints (occupied and unoccupied) as well as the desired 
temperature units (°F or °C).  Permanent setpoints are written to RAM and EEPROM 

 

Cooling setpoint 

Occupied mode 

Heating setpoint 

Occupied mode 

Cooling setpoint 

Unoccupied mode 

Heating setpoint 

Unoccupied mode 

°F or °C 

display setting 

Cooling 
set? Y/N

 

No next 

 

Yes down 

 

Heating 
set? Y/N

 

No next 

 

Yes down 

 

Unocc CL 
set? Y/N

 

No next 

 

Yes down 

 

Unocc HT 
set? Y/N

 

No next 

 

Yes down 

 

°F or °C 
set? Y/N

 

No next 

 

Yes down 

 

Use 

▲▼

 keys to set value, Yes key to confirm 

Cooling 
70.0 °F

 

Use 

▲▼

 

To set value 

Heating 
68.00 °F

 

Use 

▲▼

 

To set value 

Unocc CL 
80.0 °F

 

Use 

▲▼

 

To set value 

Unocc HT 
60.0 °F

 

Use 

▲▼

 

To set value 

Units 
°F

 

Use 

▲▼

 

To set value 

 
 

Temporary setpoint changes 

 

Temporary setpoints can be modified through the Up arrow key (

and the Down arrow keys (

). 

User will be prompted with the present mode (Heating or Cooling) of the thermostat and its setpoint. 
The Up (

arrow key will increment the setpoint by 0.5 degree (F or C). 

The Down (

)

 arrow key will decrement the setpoint by 0.5 degree (F or C). 

Press the Yes key to accept the new setpoint. 

 

Local changes to the heating or cooling setpoints made by the user directly using the up or down arrow are temporary.  
They will remain effective for the duration specified by ToccTime.  
Setpoints will revert back to their default value after internal timer ToccTime expires. 
If a permanent change to the setpoints is required, use the 

Temperat set ?

 menu 

 
 

D) Humidity setpoints 

 

 

Humidity 
set     Y/N 

 

This menu permits the adjustment of humidification and dehumidification setpoints. 

 

Dehumidification 

setpoint 

Humidification 

setpoint 

Dehumidi 
set? Y/N

 

No next 

 

Yes down 

 

Humidifi 
set? Y/N

 

No next 

 

Yes down 

 

Use 

▲▼

 keys to set value, Yes key to confirm 

Dehumidi 
70 %

 

Use 

▲▼

 

To set value 

Humidifi 
50 %

 

Use 

▲▼

 

To set value 

 

To prevent overlap, a minimum fixed deadband of 5% RH will always prevail between the humidification and dehumidification 
setpoints. For example, if the humidification setpoint is 50% RH and the dehumidification setpoint is changed from 70% RH to 
45% RH, the humidification setpoint will be modified to 45% RH by the thermostat. 
 

Humidification process 

 

Humidification process will only be allowed when the thermostat is in heating mode (System Mode  = Heat or System Mode = 
Auto and effective mode at the thermostat is heat). If there is a humidification demand and the fan is OFF, the fan is first turned 
ON and the humidifier output is then activated. 
Other than having the RH setpoint, the following events can stop the humidification process at any time: RH sensor is out of 
range, System Mode is switched to Off or Cool and the System Mode = Auto but the room’s effective mode changes from Heat 
to Cool 
 

Содержание VT7607B5x28(X)

Страница 1: ...dy VT6x7 Series LonWorks Integration Guide VYKONStat PIR Application Guide VYKONStat PIR Cover Assembly Installation Guide VYKONStat Wireless Controller Application Guide Models Available Application...

Страница 2: ...2...

Страница 3: ...er alarm will be displayed on the thermostat LCD screen when the input is energized It can be tied to a differential pressure switch that monitor filters Rem NSB remote NSB timer clock input Will disa...

Страница 4: ...push on it until the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correc...

Страница 5: ...internal wiring Jumper J1 T1 24 Vac Cool Stage 2 Y2 Y1 Jumper J1 See note 1 previous page Fan RC G C Heat Stage 1 W1 RH W2 Auxiliary Output Field contact Com 24V Remote Outdoor Sensor Digital Input 0...

Страница 6: ...hermostat Remote humidity sensor accessories Model no Description VH2020W1028 Wall mounted humidity sensor VH2020D1028 Duct mounted humidity sensor VH2020W1028 remote wall mounted room humidity sensor...

Страница 7: ...e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o...

Страница 8: ...122 F indicates a shorted sensor Associated functions such as mode lockouts are automatically disabled A minimum range status 40 C 40 F is not displayed and indicates a opened sensor or a sensor not...

Страница 9: ...increase temperature setpoint and to adjust the desired values when programming and configuring the thermostat When left unattended for 45 seconds the display will resume automatic status display scr...

Страница 10: ...will be prompted with the present mode Heating or Cooling of the thermostat and its setpoint The Up arrow key will increment the setpoint by 0 5 degree F or C The Down arrow key will decrement the set...

Страница 11: ...ehumidification output is then activated There is NO active temperature lockout protection in this mode If the dehumidification process causes the room temperature to rise or fall the thermostat will...

Страница 12: ...00 00 AM Use To set value Unoccup 00 00 AM Use To set value Sets Event 2 Unoccupied time Will activate unoccupied setpoints Use to set value Yes key to confirm Typical examples of a 2 event office sc...

Страница 13: ...e Will activate unoccupied setpoints Use to set value Yes key to confirm Ex 1 Four event retail establishment schedule Event Period 1 Event 1 Period 1 Event 2 Period 2 Event 3 Period 2 Event 4 Setpoin...

Страница 14: ...3 hours Use to set value Yes key to confirm Schedule resume Resume regular scheduling cancels the permanent hold and re enables the regular programming as set per internal scheduling or as per remote...

Страница 15: ...orking address Default value 254 Range is 0 to 254 Conditional parameter to BACnet MS TP models VT76xxX5x28B Conditional parameter to Wireless models VT76xxX5x28W This parameter will only appear when...

Страница 16: ...ut the menu part related to scheduling is disabled and no longer accessible Open contact occupied setpoints Closed contacts unoccupied setpoints RemOVR Temporary override remote contact Disables all o...

Страница 17: ...32 C Maximum occupied unoccupied heating setpoint adjustment Heating setpoint range is 40 to 90 F 4 5 to 32 0 C Cool min Minimum cooling setpoint limit Default value 54 F 12 C Minimum occupied unoccup...

Страница 18: ...or On or Auto fan mode When selecting Off the fan terminal G when heating stages terminals W1 W2 are solicited will not be energized The fan in this case will be controlled by the equipment fan limit...

Страница 19: ...toggles from occupied to unoccupied after the last movement has been detected by the PIR Range is 0 5 to 24 0 hours in 0 5 hour increments 2 4event Number of events configuration Default value 2 even...

Страница 20: ...network value is transmitted to the thermostat See RH LT RE Sp From 20 F up to 55 F 6 5 C to 13 C HL Sp RH High limit setpoint Default value 85 RH High humidity limit in the supply Only valid if a 0 1...

Страница 21: ...et that can be added subtracted to actual displayed humidity by 15 0 RH This calibration applies to the internal humidity sensor if no remote humidity sensor is connected This calibration applies to t...

Страница 22: ...e 8 RE Sp was set to 20 therefore the humidity setpoint dropped from 45 to 20 If you don t want to use this feature set the RE Sp parameter to 90 RH High limit humidity sensor The VT76x7 series includ...

Страница 23: ...etpoint mode for the new setpoint to be kept and memory and used all the time 2 Go to the Set temperature menu 3 The last prompt is setpoint type Set it to Permanent setpoint Wrong mode selected Selec...

Страница 24: ...erify wiring Digital display shows missing digits or erratic segments Defective display Replace thermostat RH sensor is out of range Verify the remote RH sensor or the internal RH sensor System Mode i...

Страница 25: ...0 Vdc into 2K resistance min Humidification analog output accuracy 3 typical Wire gauge 18 gauge maximum 22 gauge recommended Dimensions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg...