Programming and status display instructions  

 

 

1. Status display 

 

The thermostat features a two-line, eight-character display.  There is a low-level backlit level that is always active and can only 
be seen at night.  When left unattended, the thermostat has an auto scrolling display that shows the actual status of the 
system.  Each item is scrolled one by one with the backlighting off.  Pressing any key will cause the backlit to come on. 

 

Sequence of auto-scroll status display: 

 

Room Temp & 

Humidity 

 

Clock status 

 

System mode 

Schedule status 

Outdoor 

temperature 

 

Alarms 

x.x °C or °F 

 

Monday 

 

Sys mode Occupied Outdoor 

 

Service 

xx % RH 

 

12.00 AM 

 

auto 

 

x.x °C or°F 

 

 

If humidity display is 
enabled 

 

 

 

Sys mode  
off 

Occupied 
hold 

  

Frost 

ON 

RoomTemp 
x.x °C or °F 

 

 

 

Sys mode 
heat 

Unoccup 
 

  

SetClock 

If humidity display is not 
enabled

 

 

 

 

Sys mode  
cool 

Unoccup 
hold 

  

Filter 

 

 

 

 

 

Override 
 

  

Fan 

lock 

 

Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively. The last item viewed will be shown on the 
display for 30 seconds before returning to automatic scrolling. Temperature is automatically updated when scrolling is held. 

 

Outdoor air temperature display is only enabled when outdoor air temperature sensor is connected or a network value is 
received. 

  A maximum range status display of 50 °C (122 °F) indicates a shorted sensor.  Associated functions, such as mode lockouts 

are automatically disabled. 

  A minimum range status -40 °C (-40 °F) is not displayed and indicates a opened sensor or a sensor not connected. 

Associated functions, such as mode lockouts are automatically disabled. 

 
If alarms are detected, they will automatically be displayed at the end of the status display scroll.  During an alarm message 
display, the backlit screen will light up at the same time as the message and shut off during the rest of the status display.  Two 
alarms maximum can appear at any given time.  The priority for the alarms is as follows: 

 

Frost ON 

Indicates that the heating is energized by the low limit frost protection room temperature setpoint 5.6 °C (42 °F ) 

SetClock 

Indicates that the clock needs to be reset. There has been a power failure which has lasted longer than 6 hours  

Service 

Indicates that there is a service alarm as per one of the programmable digital input (DI1 or DI2) 

Filter 

Indicates that the filters are dirty as per one of the programmable digital input (DI1 or DI2) 

Fan lock 

Indicates that the heating and cooling action are locked out due to a defective fan operation 

 
Three status LEDs on the thermostat cover are used to indicate the status of the fan, a call for heat, or a call for cooling. 

 

 

When the fan is on, the FAN LED will illuminate. 

 

When heating is on, the HEAT LED will illuminate. 

 

When cooling is on, the COOL LED will illuminate. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

                                Fig.10 – VT7657 and VT7607 cover 
 

Содержание VT7607B5x28(X)

Страница 1: ...dy VT6x7 Series LonWorks Integration Guide VYKONStat PIR Application Guide VYKONStat PIR Cover Assembly Installation Guide VYKONStat Wireless Controller Application Guide Models Available Application...

Страница 2: ...2...

Страница 3: ...er alarm will be displayed on the thermostat LCD screen when the input is energized It can be tied to a differential pressure switch that monitor filters Rem NSB remote NSB timer clock input Will disa...

Страница 4: ...push on it until the tabs lock it 10 Strip each wire 1 4 inch 11 Insert each wire according to wiring diagram 13 Gently push back into hole excess wring Fig 5 14 Re Install wiring terminals in correc...

Страница 5: ...internal wiring Jumper J1 T1 24 Vac Cool Stage 2 Y2 Y1 Jumper J1 See note 1 previous page Fan RC G C Heat Stage 1 W1 RH W2 Auxiliary Output Field contact Com 24V Remote Outdoor Sensor Digital Input 0...

Страница 6: ...hermostat Remote humidity sensor accessories Model no Description VH2020W1028 Wall mounted humidity sensor VH2020D1028 Duct mounted humidity sensor VH2020W1028 remote wall mounted room humidity sensor...

Страница 7: ...e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o c c u p 1 2 0 0 p m Time Oc c u p i e d d a y Y N Oc c u p i e d 1 2 0 0 p m Time Un o...

Страница 8: ...122 F indicates a shorted sensor Associated functions such as mode lockouts are automatically disabled A minimum range status 40 C 40 F is not displayed and indicates a opened sensor or a sensor not...

Страница 9: ...increase temperature setpoint and to adjust the desired values when programming and configuring the thermostat When left unattended for 45 seconds the display will resume automatic status display scr...

Страница 10: ...will be prompted with the present mode Heating or Cooling of the thermostat and its setpoint The Up arrow key will increment the setpoint by 0 5 degree F or C The Down arrow key will decrement the set...

Страница 11: ...ehumidification output is then activated There is NO active temperature lockout protection in this mode If the dehumidification process causes the room temperature to rise or fall the thermostat will...

Страница 12: ...00 00 AM Use To set value Unoccup 00 00 AM Use To set value Sets Event 2 Unoccupied time Will activate unoccupied setpoints Use to set value Yes key to confirm Typical examples of a 2 event office sc...

Страница 13: ...e Will activate unoccupied setpoints Use to set value Yes key to confirm Ex 1 Four event retail establishment schedule Event Period 1 Event 1 Period 1 Event 2 Period 2 Event 3 Period 2 Event 4 Setpoin...

Страница 14: ...3 hours Use to set value Yes key to confirm Schedule resume Resume regular scheduling cancels the permanent hold and re enables the regular programming as set per internal scheduling or as per remote...

Страница 15: ...orking address Default value 254 Range is 0 to 254 Conditional parameter to BACnet MS TP models VT76xxX5x28B Conditional parameter to Wireless models VT76xxX5x28W This parameter will only appear when...

Страница 16: ...ut the menu part related to scheduling is disabled and no longer accessible Open contact occupied setpoints Closed contacts unoccupied setpoints RemOVR Temporary override remote contact Disables all o...

Страница 17: ...32 C Maximum occupied unoccupied heating setpoint adjustment Heating setpoint range is 40 to 90 F 4 5 to 32 0 C Cool min Minimum cooling setpoint limit Default value 54 F 12 C Minimum occupied unoccup...

Страница 18: ...or On or Auto fan mode When selecting Off the fan terminal G when heating stages terminals W1 W2 are solicited will not be energized The fan in this case will be controlled by the equipment fan limit...

Страница 19: ...toggles from occupied to unoccupied after the last movement has been detected by the PIR Range is 0 5 to 24 0 hours in 0 5 hour increments 2 4event Number of events configuration Default value 2 even...

Страница 20: ...network value is transmitted to the thermostat See RH LT RE Sp From 20 F up to 55 F 6 5 C to 13 C HL Sp RH High limit setpoint Default value 85 RH High humidity limit in the supply Only valid if a 0 1...

Страница 21: ...et that can be added subtracted to actual displayed humidity by 15 0 RH This calibration applies to the internal humidity sensor if no remote humidity sensor is connected This calibration applies to t...

Страница 22: ...e 8 RE Sp was set to 20 therefore the humidity setpoint dropped from 45 to 20 If you don t want to use this feature set the RE Sp parameter to 90 RH High limit humidity sensor The VT76x7 series includ...

Страница 23: ...etpoint mode for the new setpoint to be kept and memory and used all the time 2 Go to the Set temperature menu 3 The last prompt is setpoint type Set it to Permanent setpoint Wrong mode selected Selec...

Страница 24: ...erify wiring Digital display shows missing digits or erratic segments Defective display Replace thermostat RH sensor is out of range Verify the remote RH sensor or the internal RH sensor System Mode i...

Страница 25: ...0 Vdc into 2K resistance min Humidification analog output accuracy 3 typical Wire gauge 18 gauge maximum 22 gauge recommended Dimensions 4 94 x 3 38 x 1 13 Approximate shipping weight 0 75 lb 0 34 kg...

Отзывы: