C stage
Number of cooling stages
2 stages model only
Default value =
2 stages
Will revert the operation of 2 stage thermostat to single stage
operation only when the second cooling step is not needed.
1 or 2 stages
H lock
Outside air temperature heating
lockout
Default value =
120 °F ( 49 °C )
Disables heating stage operation based on outdoor air
temperature.
Function will only be enabled if OS ( outside air temperature
sensor ) is connected.
From -15 °F up to 120 °F ( -26 °C up to 49 °C )
C lock
Outside air temperature mechanical
cooling lockout.
Default value =
-40 °F ( -40 °C )
Disables cooling stage operation based on outdoor air
temperature.
On economizer model, free cooling will not be disabled by
this function.
Function will only be enabled if OS ( outside air temperature
sensor ) is connected.
From -40 °F up to 95 °F ( -40 °C up to 35 °C )
Unocc TM
Unoccupied Timer value
Default
0.5 hours
Time delay between the moment where the thermostat
toggles from occupied to unoccupied after the last movement
has been detected by the PIR.
Range is:
0.5 to 24.0 hours
in 0.5 hour increments
2/4event
Number of events configuration
Default value =
2 event
For scheduling model only -
VT7657B1028B
2 events
, will set up programming for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
4 events
, will set up programming for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
Event 3 is for Occupied setpoints
Event 4 is for Unoccupied setpoints
Auxiliary contact configuration
Default value =
N.O. normally open
This contact can be used to energize peripheral devices
such as: lighting equipment, exhaust fans, economizers, etc.
This contact will operate in parallel with the internal
occupied/unoccupied schedule of the thermostat or the
remote NSB contact if DI is used.
When the system is in
OFF mode
, the contact will remain in
its unoccupied status independently of the occupied /
unoccupied schedule.
Configured
Contact
occupied
status
Contact unoccupied
status
N.O.
Closed Opened
Aux cont
N.C.
opened Closed