OUTPut:REGister:POLarity
Purpose
Controls the polarity at which output data is latched to the specified port
Type
Setting
Command Syntax
OUTPut:REGister:POLarity <port #> <edge>
Command Parameters
<port #> = 0, 1, 2, 3, 4, 5
<edge> = NORMal | INVert
*RST Value
NORMal
Query Syntax
OUTPut:REGister:POLarity? <port #>
Query Parameters
<port #> = 0, 1, 2, 3, 4, 5
Query Response
NORM | INV
Description
The Output Register Polarity command controls the polarity at which output data is
latched to the specified port. A polarity of NORMal would cause the data to be latched
out on a rising edge of the clock. A Polarity of INVert would cause the data to be latched
out on a falling edge of the clock.
Note, that it is important to remember that the output register must be operating in
clocked mode in order for the polarity to affect the Output Register latching.
Examples
Command / Query
Response (Description)
OUTP:REG:POL 0 NORM
OUTP:REG:POL? 0
NORM
Related Commands
OUTPut:REGister:SOURce <port> <source>